110
6.3
Operation Mode
There are 4 operation modes:
Logo/Start-up
,
Normal Operation
,
Standby
and
Fault
modes. See section 4.3 for details of these modes.
1. Logo/Start-up
mode displays the Chint Power Systems logo when the
inverter is checking if conditions are met for connection after a manual
start-up of the inverter.
2. Normal Operation
mode is the default indication interface for normal
operation. In this mode, the inverter is converting the DC power from
the array to AC power, feeding it continuously to the grid.
3. Standby
mode is active when the output voltage and power of PV
modules do not meet the startup conditions or PV voltage and input
power are lower than the set value. The inverter will check automatically
whether it meets the startup conditions in this mode until it turns back to
Normal Operation mode.
4. Fault
mode is displayed when the inverter disconnects from the grid
due to a fault in the inverter or grid. Check the Fault log under
Current
Errors
and reference the “Troubleshooting” table in
Chapter 8
to
determine the cause of the error.
6.4
Grid-tied Power Generation
The CPS SCA50KTL-DO/US-480 and SCA60KTL-DO/US-480 series
inverters have an automatic grid-tied power generation process. It will
check constantly whether AC power grid meets the conditions for grid-tied
power generation, and test whether the PV array has adequate energy.
After all conditions are met, the inverter will enter Normal Operation mode
and export power to the grid. While generating power, the inverter can
detect the power grid at all times, supply current, matching voltage and
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...