120
Table 8-3 LCD Troubleshooting ALARM
Type
Error/State
Fault Description / Instruction
A
larm
TempSensorErr
Definition: Prompt detection of abnormal
temperature
Possible causes:
1. Temperature Sensor socket connecter has poor
contact
2. Temperature Sensor is damaged
Recommended solutions:
1. Observe temperature display
2. Switch off exernal AC disconnect, then back on
to reboot the system;
3. Contact post-sales service if not corrected
CommErr
Definition: Communication inside inverter fails
Possible causes:
Terminal block connecters of internal
communication wires have poor contact
Recommended solutions:
1. Observe for 5 minutes to see whether the alarm
will be eliminated automatically
2. Switch off exernal AC disconnect, then back on
to reboot the system
3. Contact post-sales service if not corrected
ExtFanErr
Definition: Cooling fan failure
Possible causes:
1. Fan is blocked
2. Fan service life has expired
3. Fan socket connecter has poor contact
Recommended solutions:
1. Observe for 5 minutes to see whether the alarm
will be eliminated automatically
2. Check for foreign objects on fan blades;
3. Switch off exernal AC disconnect, then back on
to reboot the system
4.Contact post-sales service if not corrected
EepromErr
Definition: Internal alarm
Possible causes:
Internal memory has a problem
Recommended solutions:
1. Observe for 5 minutes to see whether the alarm
will be eliminated automatically
2. Contact post-sales service if not corrected
Summary of Contents for SCA50KTL-DO/US-480
Page 2: ......
Page 6: ......
Page 53: ...47 Figure 3 24 Bypass Terminal option installed within the Standard wirebox ...
Page 139: ...133 Figure 10 1 CPS SCA50KTL kW and kVA derating curves of PV input voltage ...
Page 140: ...134 Figure 10 2 CPS SCA60KTL kW and kVA derating curves of PV input voltage ...
Page 141: ...135 Figure 10 2 CPS SCA60KTL Reactive Power Capability ...