19
3.2.3. Installation Space Requirement
The distances between the inverters or the surrounding objects should
meet the following conditions:
≥
300mm
(11.8in.)
≥
300mm
(11.8in.)
≥
500mm
(19.7in.)
=600mm
(23.6in.)
Note:This dimension can be modified
according to installation requirements.
NOTICE:
The spacing between two adjacently mounted inverters must be
≥19.7in (500mm). Spacing should be enlarged for installation
locations with ambient temperature higher than 45°C. Ensure that the
air space around the inverter is well ventilated. The spacing below the
inverter is intended to ensure the LCD and Keypad height are well
positioned for the user, and may be decreased, however
consideration must be taken for locations known to flood or have
seasonal snow build up.