36
1+
SPD
2+
3+
PE
AC Output:
Use 90 ¡ã
C wire, either 3~2/0AWG copper or
2~2/0AWG aluminum, torque 110 in-lbs.
AC Ground:
Use 90¡ ã
C copper wire, 6~ 4AWG for internal
grounding bar or
external grounding nut , torque 50 in-lbs.
L1
L2
L3
N
7
8
9
10
Figure 3-20(b) Internal Connection Points within the H4 wirebox
⑦
DC Input fuse holder
⑧
DC SPD (Surge Protective Device)
⑨
Internal ground terminal
⑩
AC output terminal block
3.3.3. DC Connection
3.3.3.1. Working mode
These inverters are factory configured with three MPPTs which
are electrically divided into separate PV input zones: PV Input-1,
PV Input-2, and PV Input-3. Each 5-string PV input zone
operates as a separate and independent MPP Tracker.
Independent mode can be very useful for sites with partial
shading of the array or with arrays consisting of different tilt or