50
5. Assembly process H4 connector.
Insert contact cable assembly
into back of male and female connector. A “click” should be heard or
felt when the contact cable assembly is seated in correct position.
Contacts cannot be removed once seated. See Figure 3-29 and
Figure 3-30.
Figure 3-28(a) Assemble female connector with DC positive cable
Figure 3-28(b) Assemble male connector with DC negative cable
6. Connector body tightening.
The back cap must be closed using
a torque of approx 2.7Nm (24in-lbs). Amphenol specified hand
wrench tool (H4TW0001) can be used in this step with the
Amphenol open-end back cap spanner (H4TE0000) or socket
wrench (H4TF000) as shown in Figure 3-31.