65
INSTALLATION DRAWINGS
AND LINEAR CONFIGURATION
FREE-STANDING DIMENSIONS (MM) - BOILERS & FRAME ONLY
NO. OF BOILERS
2
3
4
5
6
7
8
Width mm
1310
1940
2570
3200
3830
4460
5090
Note This information is provided as a guide only. Please refer to the Quinta Pro Cascade Installation and Service Manual for specific details.
Two to eight Quinta Ace 135 and 160 boilers in a linear
configuration, mounted on a free-standing frame.
KEY
A
System Flow; Connection DN 125 /
DIN 2633 (8 holes)
X
Distance to system return
connection = 200mm
Gas supply connection DN65 /
DIN 2633 (4 holes)
Air inlet/flue gas discharge
concentric connection – 100 / 150mm
B
System Return; Connection DN 125 /
DIN 2633 (8 holes)
Y
Distance to system flow
connection = 560mm
OV
Low loss header
DN 100 = 633mm
QUINTA
ACE 135 AND 160
STRUCTURE OF QUINTA ACE 135 AND 160
CASCADE SYSTEMS
Complete cascade options are available for the Quinta Ace 135 and 160 with both insulated and non-insulated versions.
Note: Mixed cascades are also available (eg. QA135 or 160 in conjunction with QA30 - 115).