Operating Procedures
Daily Shut-Down Procedures
1. Set the On/Off switch to the Off position.
2. Unplug the power cord from the receptacle.
3. Set the outlet pressure to zero on the regulator.
4. Remove any air tools or accessories.
5. Open the drain valve allowing air to bleed from
the tank. After all of the air has bled from the tank,
close the drain valve to prevent debris buildup in
the valve.
When draining the tank, always use ear and eye
protection. Drain the tank in a suitable location;
condensation will be present in most cases of
draining.
Water that remains in the tank during storage will
corrode and weaken the air tank which could cause
the tank to rupture. To avoid serious injury, be sure
to drain the tank after each use or daily.
WARNING
CAUTION
Daily Start-Up Procedures
1. Set the On/Off switch to the Off position.
2. Inspect the air compressor, air hose, and any
accessories/tools being used for damage
or obstruction. If any of these mentioned items
are in need of repair/replacement, take the unit to a
qualified service dealer for inspection and repair
using identical replacement parts.
3. Close the drain valve.
4. Connect the air hose to the quick connect socket
on the regulator assembly by inserting the
quick connect plug on the air hose into the
quickconnect socket. The quick connect socket
collar will snap forward and lock the plug into
place providing an air tight seal between the
socket and plug. To release the air hose push the
collar back on the quick connect socket.
5. Plug the power cord into the proper receptacle.
6. Turn the On/Off switch to the On position and the
compressor will start and build air pressure in the
tank to cut-out pressure and then
shut off automatically.
7. Adjust the regulator to a PSI setting that is needed
for your application and be sure it is within the
safety standards required to perform the task.
If using a pneumatic tool, the manufacturer
should have recommendations in the manual for
that particular tool on operating PSI settings.
8. The air compressor is now ready for use.
5
3
7
5
4
1
6