Snack / Refreshment Center Setup and Operator's Guide
Page 5
1670001
April, 1999
The merchandiser is supplied with a service cord for the country of use and is terminated in a grounding type
plug. The wall receptacle used for this merchandiser must be properly polarized, grounded, and of the correct
voltage. Operating the merchandiser from a source of low voltage will
VOID YOUR WARRANTY
. Each mer-
chandiser should have its own electrical circuit and that circuit should be protected with a circuit breaker or
fuse conforming to local regulations.
Voltage Check -
Place the leads of a voltmeter across the LINE (LIVE) and NEUTRAL ter-
minals of the wall receptacle. The voltmeter should indicate 110-130 volts ac for 120 volt,
60 Hz locations, or 220- 240 volts ac for 230 volt, 50 Hz locations.
Polarity Check -
Place the leads of a voltmeter across the LINE (LIVE) and GROUND ter-
minals of the wall receptacle. The voltmeter should indicate 110-130 volts ac for 120 volt,
60 Hz locations, or 220- 240 volts ac for 230 volt, 50 Hz locations.
Noise Potential Check -
Place the test leads of a voltmeter across the NEUTRAL and
GROUND terminals of the wall receptacle. The meter should indicate 0 volts ac. A mea-
surement greater than 1.5 - 2.0 volts ac could result in problems for the merchandiser' s
electronic circuitry caused by electrical noise.
Any deviation from these requirements could result in unreliable performance from your merchandiser.
Remove all packing materials from the interior of the machine. Keep all documents; warranty cards, etc.
Set aside the base plate kit (if present).
!"#$%& '$()*%$+$,-.
/,0123& -4$& 5124*,$
Summary of Contents for 787E
Page 2: ......