ELECTRICAL CHECK (cont.)
Meg-Ohm Insulation Check Taken at Control Panel with Power Off:
Red/Ground
Black/Ground
White/Ground
NOTE:
Readings of 5 and higher are acceptable. “0” Reading indicates A Dead Short.
PERFORMANCE CHECK
NOTE:
With Pump Power OFF fill basin with a minimum of thirty-two inches of water.
NEXT: Turn the power ON.
Is the high water alarm on:
YES
NO
When alarm light turns “OFF”, turn power off at control panel.
Did the alarm shut off with a water depth of approx. 26 inches:
YES
NO
Turn power back ON, record amperage readings.
Single Phase:
Amperage Load at Line Connection with Pump on: L1
Amps L2
Amps
NOTE: Reading should be within 10% of name plate amp rating.
Three Phase:
Is Pump Rotation Correct (CCW viewed from bottom):
YES
NO
Amperage Load at Line Connection with Pump on:
L1
Amps L2
Amps L3
Amps
NOTE: Reading should be within 10% of name plate amp rating.
Did the Pump Shut Off with a Water Depth of Approx. 10 Inches:
YES
NO
Are There Any Visible Leaks Within the Basin:
YES
NO
Equipment’s Difficulties During Start Up:
FINAL CHECK
Has the End User Received all Operation Manuals:
YES
NO
Has End User Been Briefed on Warranty:
YES
NO
Are the Operation & Maintenance Manual(s) Saved for Future Use:
YES
NO
Where Are They Being Kept:
I Have Received the Above Information/Instructions: (name of owner/operator)
Signature:
Date:
Address of Local Barnes Distributor
I certify this report to be accurate: (name of start up person)
Signature:
Date:
Employed By:
REPORTS NOT RETURNED CAN DELAY OR VOID WARRANTY
.