Installing your Cooker Hood
5
Your new Cooker Hood can be installed either
for recirculation or extraction through an
outside wall.
Installation:
These distances, between hobs and grease
filter must be observed.
Minimum 65cm
over an electric hob.
Minimum 75cm
over a gas hob.
Minimum 40-45cm over a high level grill/
top oven.
See page 7.
Installation for Recirculation:
If it is not possible to exhaust to the outside,
the hood can be used to filter and recirculate
the air (Fig.1).
-
To set deflector ready for extraction, slide
the conversion control towards the outside
of the conveyor until index C is visible
(Fig.2a).
-
To set deflector ready for recirculation,
slide the control towards the inside of the
conveyor (Fig.2b). Pull the plastic tongue
that blocks the index C outwards, to make
the insertion of the deflector easier. Fit the
supplied cover on the upper outlet hole.
NOTE: The hood is more efficient in the
exhaust mode, therefore this position
should be selected during the warmer
months of the year when no heating is
being used. When the room is being
heated, if the recirculation position is
selected heat will not be wasted.
To obtain the best performance it is
advisable to switch on the hood a few
minutes before you start cooking and leave
it running approximately 15 minutes after
finishing.
Installation for Extraction:
This method is recommended if at all possible.
Fumes and grease laden air are drawn into the
underside of the hood and expelled out.
The air can be expelled either upwards
through a ventilating shaft (Fig.3 A) or directly
through the wall to the outside (Fig.3 B).
Ducting will be required if the Cooker Hood is
mounted away from the outside vent.
To connect the pipe, fit the coupling ring
(Fig.3 C) in the selected outlet. Use the cover
(Fig.3 D) to close the unused outlet.
IMPORTANT: The exhaust air must not be
expelled through a smoke or waste-gas
chimney which is in use or through a shaft
used for ventilating rooms or into the
cavity of a cavity wall.
If the room contains a flued fuel burning
appliance, such as a gas or oil fired central
heating boiler, which is not of the ‘Balanced
Flue’ type, you should make sure that there
is adequate air inlet into the room at all
times so that fumes from the boiler are not
drawn back into the room by the Cooker
Hood.
NOTE: All installations must comply with
local authorities and building regulation
requirements for the discharge of exhaust
air into the atmosphere.
Fig.1
Fig.2
Fig.3
Extraction
Recirculation
Fig.2a
Fig.2b