Uninterruptible Power Supply
Crestron
CEN-UPS1250
CEN-UPS1250 Specifications (Continued)
SPECIFICATION DETAILS
Battery
Internal
Battery
(1) Crestron model CEN-UPS1250-BTP battery
pack included, composed of (4) 12 Volt, 9 Ah
maintenance-free sealed lead acid with
suspended electrolyte
Backup
Runtime
~12 minutes @ half load (625 W),
~2.7 minutes @ full load (1250 W)
Recharging
Time
~8 hours typical to 90% capacity following a
discharge to shutdown @ half load
Battery Life
2 to 5 years under normal use
Ethernet
10BASE-T/100BASE-TX, auto switching, auto
negotiating, auto discovery, full/half duplex,
TCP/IP, UDP/IP, CIP, DHCP, IEEE 802.3U
compliant
Alarm
Audible alarm indicates when in backup mode,
when battery is low and when overloaded
Minimum 2-Series Control
System Update File
1, 2
Version 3.155.1240 or later
Environmental
Temperature
32º to 104ºF (0º to 40ºC)
Humidity
10% to 90% RH (non-condensing)
Heat Dissipation
100 BTU/Hr
Enclosure
Chassis
Steel, black matte powder coat finish
Cooling
Microprocessor controlled ultra quiet rear facing
fan, vented sides
Faceplate
Extruded aluminum, black matte powder coat
finish with polycarbonate label overlay
Mounting
Freestanding or 3U 19” rack mountable, rack
must be four post type up to 28” maximum
depth (removable feet and rack mount kit
included)
Dimensions
Height
5.21 in (133 mm) without feet
5.54 in (141 mm) with feet
Width
17.02 in (433 mm) without ears
19.11 in (486 mm) with ears
Depth
19.73 in (501 mm)
Weight (approximate)
62 lbs (28.2 kg)
Included Accessory
CEN-UPS1250-BTP
Internal Battery Pack
1. The latest software versions can be obtained from the Crestron Web site. Refer to the NOTE
following these footnotes.
2. Crestron 2-Series control systems include the AV2 and PRO2. Consult the latest Crestron Product
Catalog for a complete list of 2-Series control systems.
NOTE:
Crestron software and any files on the Web site are for authorized Crestron
dealers and Crestron Authorized Independent Programmers (CAIPs) only. New users
must register to obtain access to certain areas of the site (including the FTP site).
4
•
Uninterruptible Power Supply: CEN-UPS1250
Operations & Installation Guide – DOC. 6635E