Uninterruptible Power Supply
Crestron
CEN-UPS1250
“LED DIMMER” Screen
LED DIMMER:HIGH
PRESS TO CHANGE
GO TO BAT IF < XXXV setting – This screen allows setting a low voltage
threshold for the unit, which forces it to switch to power from the internal battery
pack when the threshold is reached. Settings range from 92 to 100 Volts.
“GOTO BAT IF < XXV” Screen
GOTO BAT IF < 100V
PRESS TO CHANGE
GO TO BAT IF > XXXV setting – This screen allows setting a high voltage
threshold for the unit, which forces it to switch to power from the internal battery
pack when the threshold is reached. Settings range from 134 to 142 Volts.
“GOTO BAT IF > XXV” Screen
GOTO BAT IF > 134V
PRESS TO CHANGE
OUTLET DELAY1 and OUTLET DELAY2 setting – These settings define a time
delay (0 to 10 seconds) for when the unit provides power to the rear panel outlets
marked BANK 3 and BANK 4 respectively. Setting this delay prevents power on or
power off glitches from affecting other equipment connected to the unit.
“OUTLET DELAY1” Screen
OUTLET DELAY1:5SEC
PRESS TO CHANGE
“OUTLET DELAY2” Screen
OUTLET DELAY2:5SEC
PRESS TO CHANGE
LOWBATWARNING setting – This screen allows setting the unit to sound an alarm
and illuminate the
LOW BATT
LED on the front panel whenever the battery pack’s
estimated runtime remaining drops to or below the programmed setting (2 to 26
minutes).
“LOWBATWARNING” Screen
LOWBATWARNING:2MIN
PRESS TO CHANGE
BATREPDATE setting – This function allows entry of the exact date a replacement
battery pack is installed in the unit. First, use the up/down arrow buttons to set the
correct month, then press the
SETUP
button to move the cursor to the day of the
month field. Set the day of the month using the up/down arrow buttons. Press the
SETUP
button to move the cursor to the year field. Set the year using the up/down
arrow buttons.
28
•
Uninterruptible Power Supply: CEN-UPS1250
Operations & Installation Guide – DOC. 6635E