Terminal Block & Module   

Crestron 

CLT- & CLX-2DIM2

 

NOTE:  

Unless otherwise indicated, the lighting 

system specified in this guide is modular, requiring 
assembly in the field by a licensed electrician, in 
accordance with all national and local codes. 
If you require a UL Listed panel, Crestron offers this 
service through its UL Listed panel shop. This 
includes complete in factory system configuration 
and assembly by Crestron for an additional fee.  

Terminal Block Installation and Field 
Wiring 

1.  Use the two supplied self-tapping pan Phillips 

screws (8B x ¼ length) to secure the terminal 
block and the appropriate (left or right) wiring 
label to the Crestron Automation Enclosure. The 
wiring label lies beneath the terminal block as 
shown in the two wiring diagrams on this page. 

NOTE:  

Both left and right wiring labels are 

provided. The left-side labels are common for both 
single and double-wide enclosures. The right-side 
labels are only used in double-wide enclosures since 
the modules and terminal blocks along the right side 
must be inverted when mounting. 

 

CAUTION:  

Bypass jumpers are provided to allow 

testing of circuits and to protect the module during 
installation. When properly secured by two screws, 
the jumpers on the black and red sections of the 
terminal block short the hot to dim so that all circuits 
are energized. Furthermore, the jumpers on the white 
sections of the terminal block tie the neutrals 
together. Do not remove any bypass jumpers until all 
feed and load wiring has been completed, the circuit 
has been tested for electrical faults, and the module 
has been installed. Refer to “Module Installation” on 
next page. 

NOTE:  

Use copper conductors only – rated 75

°

2.  With the circuit breaker turned off, connect the 

circuit feed (HOT and NEUTRAL) and 
controlled circuit (LOAD) wires to the terminal 
block per the markings provided on the wiring 
label (as shown in the diagrams on this page). 
Terminal blocks accept one 14 - 10 AWG wire. 
Wires should be stripped to ½ inch. Tighten 
terminal blocks to 9 in-lbs. Do not over tighten.  

3.  Grounding terminal blocks are available in the 

cabinet for termination of ground wires. Tighten 
to 35 in-lbs. (14 – 10 AWG), 40 in-lbs.  
(8 AWG), or 45 in-lbs. (6 – 4 AWG).  

4.  Test the circuit for electrical faults by turning on 

the circuit breaker and checking that the breaker 

does not trip and that the proper lighting loads 
are energized.  

Wiring Diagram of the Terminal Block to the Feed and 
Load(s)(Single-wide and Left Side Double-wide Enclosures) 

             

NEUTRAL

HOT 1

(FROM 15 OR 20 AMP 

CIRCUIT BREAKER)

TERMINAL

BLOCK

LEFT SIDE

WIRING LABEL

TO

LOAD 1

AREA FOR

MODULE

LOCATION

LABEL

GROUNDING

TERMINAL

BLOCK

GND

TO

LOAD 2

BYPASS

JUMPERS

NEUTRAL

HOT 2

(FROM 15 OR 20 AMP 

CIRCUIT BREAKER)

 

 

Wiring Diagram of the Terminal Block to the Feed and 
Load(s) (Right Side Double-wide Enclosures) 

             

NEUTRAL

AREA FOR

MODULE

LOCATION

LABEL

NEUTRAL

HOT 1

(FROM 15 OR 20 AMP 

CIRCUIT BREAKER)

GROUNDING

TERMINAL

BLOCK

GND

TO

LOAD 1

TO

LOAD 2

TERMINAL

BLOCK

RIGHT SIDE

WIRING LABEL

BYPASS

JUMPERS

HOT 2

(FROM 15 OR 20 AMP 

CIRCUIT BREAKER)

 

2  

  Terminal Block & Module:  CLT- & CLX-2DIM2 

Installation Guide – DOC. 5988B 

Summary of Contents for CLT-2DIM2

Page 1: ...lock and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a well ventilated area The ambient temperature must be 32 F to 104 F 0 C to 40 C The relative humidity must be 0 to 90 non condensing Terminal blocks are installed along the l...

Page 2: ...mpers until all feed and load wiring has been completed the circuit has been tested for electrical faults and the module has been installed Refer to Module Installation on next page NOTE Use copper conductors only rated 75 C 2 With the circuit breaker turned off connect the circuit feed HOT and NEUTRAL and controlled circuit LOAD wires to the terminal block per the markings provided on the wiring ...

Page 3: ...the terminal to which it should be connected Wires are pre stripped to inch Tighten to 9 in lbs Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the module...

Page 4: ...es following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from ...