background image

 

CLTI- & CLXI-2DIM8

 

Functional Summary 

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

The Crestron

®

 2-Feed, 8-Dimmer Terminal Block and 

Module (CLTI-2DIM8 and CLXI-2DIM8, respectively), 
are considered a single entity and must be used together. 
They ship separately to permit termination of the field 
wiring to the CLTI-2DIM8 prior to installation of the 
CLXI-2DIM8, as described in this guide. They can be 
mounted in any Crestron Automation Enclosure (CAEN-
Series Enclosures). The terminal block is designed to 
terminate two circuit feeds (HOT and NEUTRAL) and 
distribute the controlled circuits (LOAD) to the fixtures. 
The module connects to the terminal block and performs 
dimming control of eight incandescent, magnetic low 
voltage, neon, cold cathode, or dimmable 2-wire 
fluorescent lighting loads. The maximum load is 10 amps 
for any single controlled circuit, or 13 amps for each 
group of four circuits, and 26 amps maximum total per 
module. The unit requires 230VAC 50 Hz, 1 phase input 
voltage. An oversize heat sink dissipates heat efficiently. 
There are LEDs on the module to indicate communication 
to a Cresnet

®

 network, input power to the module, and 

output power to the load. 

Terminal Block & Module Locations (Single-wide Enclosure) 

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

MODULE

 

NOTE:

  The two input lines must be the same phase 

or split phase. 

NOTE:  

When connecting to an Arc Fault Breaker, 

the load should not exceed 1000 watts.  

Terminal Block & Module Locations (Double-wide Enclosure) 

TERMINAL BLOCK

(RIGHT)

GROUNDING TERMINAL BLOCKS

TERMINAL BLOCK

(LEFT)

MODULE

 

Installation 

The terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
0

°

C to 40

°

C (32

°

F to 104

°

F). The relative humidity 

must be 0% to 90% (non-condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6411

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2013809)

   

Tel: 888.CRESTRON

 

11.05

   

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for CLTI-2DIM8

Page 1: ...de Enclosure TERMINAL BLOCK GROUNDING TERMINAL BLOCK MODULE NOTE The two input lines must be the same phase or split phase NOTE When connecting to an Arc Fault Breaker the load should not exceed 1000 watts Terminal Block Module Locations Double wide Enclosure TERMINAL BLOCK RIGHT GROUNDING TERMINAL BLOCKS TERMINAL BLOCK LEFT MODULE Installation The terminal block and module must be mounted into a ...

Page 2: ...ll circuits receive power Do not remove these bypass jumpers until all feed and load wiring has been completed the circuit has been tested for electrical faults and the module has been installed Refer to Module Installation on next page Jumpers are also installed on the blue sections of the terminal block and tie all neutrals together These jumpers should never be removed Wiring Diagram of the Ter...

Page 3: ...l to which it should be connected Wires are pre stripped to 12 mm Tighten to 1 Nm Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the module interconnect ...

Page 4: ...following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from the...

Reviews: