background image

 

CLTI- & CLXI-4HSW4

 

Terminal Block & Module Locations (Single-wide Enclosure) 

Functional Summary 

MODULE

TERMINAL

BLOCK

GROUNDING

TERMINAL

BLOCK

 

The Crestron

 4-Feed, 4-High-Inrush Switch Terminal 

Block and Module (CLTI-4HSW4 and CLXI-4HSW4, 
respectively), are considered a single entity and must be 
used together. They ship separately to permit termination 
of the field wiring to the CLTI-4HSW4 prior to 
installation of the CLXI-4HSW4, as described in this 
guide. They can be mounted in any Crestron Automation 
Enclosure (CAEN-Series Enclosures). The terminal block 
is designed to terminate four circuit feeds (HOT and 
NEUTRAL) and distribute the controlled circuits (LOAD) 
to the fixtures. The module connects to the terminal block 
and performs switching (non-dim) control of four 
incandescent, low voltage, neon, cold cathode, 
fluorescent, or HID lighting loads, or motor loads. The 
maximum load is 8 amps (1 HP) for each controlled 
circuit (32 amps total per module). The unit requires 
230VAC 50 Hz input voltage. An oversize heat sink 
dissipates heat efficiently. There are LEDs on the module 
to indicate communication to a Cresnet

 network, input 

power to the module, and output power to the load. 

NOTE:  

When connecting to an Arc Fault Breaker, 

the load should not exceed 1000 watts.  

Terminal Block & Module Locations (Double-wide Enclosure) 

Installation 

GROUNDING TERMINAL BLOCKS

MODULE

TERMINAL BLOCK

(LEFT)

TERMINAL BLOCK

(RIGHT)

 

Terminal block and module must be mounted into a 
Crestron Automation Enclosure by a licensed electrician, 
in accordance with all national and local codes.  

CAUTION:  

This equipment is for indoor use only 

and needs to be air-cooled. Mount in a well-
ventilated area. The ambient temperature must be 
0

°

C to 40

°

C (32

°

F to 104

°

F). The relative humidity 

must be 0% to 90% (non-condensing).  

Terminal blocks are installed along the left side of single-
wide enclosures and along the outside edges (left and 
right sides) of double-wide enclosures. Modules are 
installed along the right side of single-wide enclosures 
and side-by-side in the center of double-wide enclosures. 
When installing modules and terminal blocks in a double-
wide enclosure, be sure to invert units on the right side so 
that they can be properly wired. Refer to the illustrations 
shown in the next column when considering the location 
of terminal blocks and modules within an enclosure.  

NOTE:  

Modules and terminal blocks must be 

installed into the lowest available spaces and 
continue toward the top of the enclosure. 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6412

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2013808)

 

Tel: 888.CRESTRON

 

11.05

 

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for CLTI-4HSW4

Page 1: ... not exceed 1000 watts Terminal Block Module Locations Double wide Enclosure Installation GROUNDING TERMINAL BLOCKS MODULE TERMINAL BLOCK LEFT TERMINAL BLOCK RIGHT Terminal block and module must be mounted into a Crestron Automation Enclosure by a licensed electrician in accordance with all national and local codes CAUTION This equipment is for indoor use only and needs to be air cooled Mount in a...

Page 2: ...t shorts the hot to switch so that the circuit is receiving power Do not remove any bypass jumpers until all feed and load wiring has been completed the circuit has been tested for electrical faults and the module has been installed Refer to Module Installation on the next page Jumpers are also installed on the blue sections of the terminal block and tie the neutrals together These jumpers should ...

Page 3: ...or as the terminal to which it should be connected Wires are pre stripped to 12 mm Tighten to 1 Nm Do not over tighten 3 If the module is being installed above another module within the enclosure attach the supplied module interconnect cable between the two modules The illustration below depicts the area within a double wide enclosure where the corners of four modules meet NOTE One wire on the mod...

Page 4: ...following repair of items under warranty shall be paid by CRESTRON shipping by standard ground carrier In the event repairs are found to be non warranty return freight costs shall be paid by the purchaser CRESTRON Limited Warranty CRESTRON ELECTRONICS Inc warrants its products to be free from manufacturing defects in materials and workmanship under normal use for a period of three 3 years from the...

Reviews: