Crestron 

CSA-PWS300/600-CAEN

 

Power Supply for Crestron

®

 Shades

 

8  

  Power Supply for Crestron

®

 Shades:  CSA-PWS300/600-CAEN 

Installation Guide – DOC. 7407A 

Problem Solving 

Troubleshooting 

The following table provides corrective action for possible trouble situations. If further assistance is required, please contact a 

Crestron customer service representative.  

CSA-PWS300/600-CAEN Troubleshooting 

TROUBLE 

POSSIBLE CAUSE(S) 

CORRECTIVE ACTION 

Power LED (

PWR

does not illuminate. 

CSA-PWS300/600-CAEN is not receiving 

power.  

Verify that device is power.  

Unit is not plugged in. 

Plug in unit. 

Power

 

switch is not in correct position. 

Verify that the switch is in the 

PWR ON

 position. 

System overload 

LED (

OVRLD

) is 

illuminated.  

Unit is in slave configuration and power 

cable is not connected. 

Connect power cable. 

Total power draw from unit exceeds 300  

Watts. 

Remove excessive load and press system 

RESET

 button. 

Combination of high ambient temperature 

and excessive load. 

Place unit in a well-ventilated area, reduce load, 

press system 

RESET

 button. May also require 

cycling of power switch. 

Check Network Wiring 

Use the Right Wire

 

To ensure optimum performance over the full range of the installation topology, use 

Crestron Certified Wire only. Failure to do so may incur additional charges if 

support is required to identify performance deficiencies because of using improper 

wire. 

Calculate Power

 

CAUTION:

  Use only Crestron power supplies for Crestron equipment. Failure to 

do so could cause equipment damage or void the Crestron warranty. 

CAUTION:

  Provide sufficient power to the system. Insufficient power can lead to 

unpredictable results or damage to the equipment. Use the Crestron Power 

Calculator to help calculate how much power is needed for the system 

(

www.crestron.com/calculators

). 

When calculating the length of wire for a particular Cresnet run, the wire gauge and 

the Cresnet power usage of each network unit to be connected must be taken into 

consideration. Use Crestron Certified Wire only. The wire gauge and the Cresnet 

power usage of the run should be used in the following equation to calculate the 

cable length value on the equation’s left side. 

Cable Length Equation 

L = Length of run (or chain) in feet

R = 6 Ohms (Crestron Certified Wire: 18 AWG (0.75 mm  ))

or 1.6 Ohms (Cresnet HP: 12 AWG (4 mm  ))

P = Cresnet power usage of entire run (or chain)

2

2

L < 40,000

R x P

Where:

 

Make sure the cable length value is less than the value calculated on the right side of 

the equation. For example, a Cresnet run using 18 AWG Crestron Certified Wire and 

drawing 20 watts should not have a length of run more than 333 feet (101 meters). If 

Cresnet HP is used for the same run, its length could extend to 1250 feet (381 

meters). 

Summary of Contents for CSA-PWS300-CAEN

Page 1: ...ying an external 24V DC signal to the NET port Reset 1 8 8 Miniature push buttons each resets its respective output channel or momentarily disables the channel while held System Reset 1 Miniature push button resets all output channels sequentially or momentarily disables all channels while held Setup Not used LED Indicators PWR 1 8 8 Green LEDs indicate 24 VDC power present at each channel output ...

Page 2: ... and found to comply with the limits for a Class B digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio comm...

Page 3: ...32 in 156 mm 2 1 2 in 64 mm 1 2 14 mm TYP 1 7 16 in 37 mm 1 in 26 mm 7 3 4 in 197 mm 7 3 4 in 197 mm 6 5 32 in 156 mm Qty 2 Ø 1 3 4 in 44 mm Knockouts Ø 7 8 in 22 mm Knockouts for 1 2 13 mm conduit Typ 16 3 32 in 409 mm 4 5 16 in 110 mm 2 13 32 in 61 mm 1 5 32 in 61 mm 15 16 in 24 mm 1 1 4 in 32 mm 4 3 32 in 104 mm 2 1 2 in 64 mm 1 1 8 in 29 mm 14 11 32 in 364 mm 4 in 102 mm Qty 12 Ø 3 16 in 5 mm ...

Page 4: ...ion Guide DOC 7407A CSA PSW300 CAEN Overall Dimensions without Front Cover Qty 4 Ø 5 16 8 mm Mounting Holes Qty 4 Ø 5 8 16 mm Mounting Holes Install Cresnet Connectors as Shown 8 Outputs Maximum for each Power Supply Barcode Label Ground Bus 10 27 32 in 275 mm 1 3 4 in 45 mm 2 5 32 in 55 mm 9 32 in 7 mm Typ 18 19 32 in 472 mm ...

Page 5: ...A PWS300 600 CAEN 5 CSA PSW600 CAEN Overall Dimensions without Front Cover 10 27 32 in 275 mm 1 3 4 in 45 mm 2 5 32 in 55 mm 9 32 in 7 mm Typ 18 19 32 in 472 mm Qty 4 Ø 5 16 8 mm Mounting Holes Qty 4 Ø 5 8 16 mm Mounting Holes Install Cresnet Connectors as Shown 8 Outputs Maximum for each Power Supply Barcode Label Ground Bus ...

Page 6: ...The CSA PWS300 600 CAEN attaches to a mounting surface using four standard screws appropriate for the mounting scenario Once the unit is properly secured to the mounting surface the units must be properly wired Refer to Wiring below for details Wiring CAUTION All power feeds must be protected by 15 or 20 Amp circuit breakers not supplied NOTE Use copper conductors only rated 60 C NOTE All wiring m...

Page 7: ...nd power supply is limited by voltage drop along cable The following limits should be observed for reliable performance Maximum length of Cresnet cable between power supply and shade Cresnet P Plenum Rated 2x 18 Power 2x 22 Twisted Data 130 ft 40 m Cresnet NP 2x 18 Power 2x 22 Twisted Data 130 ft 40 m Cresnet HP NP 2x 12 Power 2x 22 Twisted Data 500 ft 153 m Maximum total length of Cresnet cable r...

Page 8: ...ncur additional charges if support is required to identify performance deficiencies because of using improper wire Calculate Power CAUTION Use only Crestron power supplies for Crestron equipment Failure to do so could cause equipment damage or void the Crestron warranty CAUTION Provide sufficient power to the system Insufficient power can lead to unpredictable results or damage to the equipment Us...

Page 9: ...ds 20 or when the combined total length of Cresnet cable exceeds 3000 feet 914 meters Further Inquiries To locate specific information or resolve questions after reviewing this guide contact Crestron s True Blue Support at 1 888 CRESTRON 1 888 273 7876 or refer to the listing of Crestron worldwide offices on the Crestron Web site www crestron com offices for assistance within a particular geograph...

Page 10: ... directly from Crestron or an authorized Crestron dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any Crestron shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it was intended or if it has been subjected to misuse accidental damage modification or improper ins...