background image

 

GLA-PWSI50

 

Crestron Electronics, Inc.

 

Installation Guide – DOC. 6747A

 

15 Volvo Drive   Rockleigh, NJ 07647

 

(2022674)

   

Functional Summary 

The GLA-PWSI50 is a 50 Watt Cresnet

®

 Power Supply 

designed for use with a Crestron

®

 Green Light™ system, 

or anywhere a wall-mountable Cresnet power supply is 
needed. It is compatible with any line voltage from 100 to 
240 Volts, 50 or 60 Hz. 

The GLA-PWSI50 mounts conveniently over the front of 
an electrical box, with all connections made inside the 
box via flying leads using terminal block connectors. An 
adapter plate is included for installation over a 1 or  
2-gang UK or Euro style electrical box. Without the 
adapter plate, the GLA-PWSI50 may be mounted over a 4 
inch square or 2-gang US electrical box. 

 

50 Watt Cresnet power supply  

 

Powers the IPAC and other Cresnet devices 

 

Provides backup power for Crestron Green Light 
cabinets 

 

Compatible with 100 to 240 VAC mains 

 

Mounts to a 1 or 2-gang UK (BS 4662) or Euro 
(DIN 49073) electrical box 

 

Also compatible with 4 inch square or 2-gang US 
electrical boxes 

GLA-PWS50 (shown with Adapter Plate) Physical View 

 

Specifications 

GLA-PWSI50 Specifications 

SPECIFICATION DETAILS 

Output Power 

 Output 

Power 

 
 

 Ripple/Noise 

 

50 Watts (2.1 Amps) @ 24 Volts 
DC, regulated, limited power 
source  

<1%  

Power Requirements 

 Input 

 

0.6 Amps @ 100-240 Volts AC, 
50/60 Hz 

Enclosure 

Metal construction, 1- or 2-gang 
(BS4662 UK or DIN 49073) 
backbox, includes adapter plate 

Environmental 

 Temperature 

 Humidity 
 

 Heat 

Dissipation 

 

0° to 40°C (32° to 104°F) 

10% to 90% RH  
(non-condensing) 

26 BTU/Hr 

Dimensions 
(without adapter plate) 
 Height 
 Width 
 Depth 

 
 
10.16 cm (4.00 in) 
14.09 cm (5.55 in) 
5.76 cm (2.27 in) 

Weight 

0.54 kg (1.2 lbs) 

Tel: 888.CRESTRON

 

02.09

   

Fax: 201.767.7576

  

Specifications subject to 

 

www.crestron.com

 

change without notice.

 

Summary of Contents for GLA-PWSI50

Page 1: ...PAC and other Cresnet devices Provides backup power for Crestron Green Light cabinets Compatible with 100 to 240 VAC mains Mounts to a 1 or 2 gang UK BS 4662 or Euro DIN 49073 electrical box Also compatible with 4 inch square or 2 gang US electrical boxes GLA PWS50 shown with Adapter Plate Physical View Specifications GLA PWSI50 Specifications SPECIFICATION DETAILS Output Power Output Power Ripple...

Page 2: ...al installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determ...

Page 3: ...tt Cresnet Power Supply Application The following diagram shows a GLA PWSI50 module in a typical application GLA PWSI50 in a Lighting Application Installation Guide DOC 6747A Wall Mount 50 Watt Cresnet Power Supply GLA PWSI50 3 ...

Page 4: ...red Crestron device 3 FUSE DC output fuse T3 15AH 5x20mm 250V 3 15A time lag ceramic cartridge 4 24VDC LED 1 green LED indicates 24 Volts DC output extinguishes when fuse is blown Setup Important Notes Read before installation Permits An electrical permit shall be obtained prior to each installation Codes Install in accordance with all local and national electrical codes Wiring Use 75 C copper wir...

Page 5: ...Not Supplied Bottom 1 M3 5x25 Supplied B 2 GANG BS 4662 UK BACKBOX 2 M3 5 Not Supplied C 1 GANG DIN 49073 BACKBOX 2 M3 Not Supplied D 2 GANG DIN 49073 BACKBOX 4 M3 Not Supplied Hardware Hookup WARNING RISK OF SERIOUS PERSONAL INJURY Turn off power at the circuit breaker s prior to installation Installing with power on can result in serious personal injury and damage to the device 1 Use the include...

Page 6: ...ailure to do so may cause damage to the GLA PWSI50 FUSE TYPE 5 x 20mm 3 15A Time Lag 5 Insert the fuse holder into the GLA PWSI50 6 Push in the fuse holder with a flat head screwdriver While pushing in the fuse holder turn the screwdriver clockwise until the fuse holder sinks in 7 Push in the fuse holder a little further and turn the screwdriver clockwise until the fuse holder locks in place 8 Con...

Page 7: ...days batteries and incandescent lamps are not covered This warranty extends to products purchased directly from CRESTRON or an authorized CRESTRON dealer Purchasers should inquire of the dealer regarding the nature and extent of the dealer s warranty if any CRESTRON shall not be liable to honor the terms of this warranty if the product has been used in any application other than that for which it ...

Page 8: ...50 Watt Cresnet Power Supply Crestron GLA PWSI50 This page is intentionally left blank 8 Wall Mount 50 Watt Cresnet Power Supply GLA PWSI50 Installation Guide DOC 6747A ...

Reviews: