background image

The Crestron® GLS-LCCT SolarSync™ photosensor measures the 

correlated color temperature (CCT) and illuminance (lux) of outdoor, 

natural sunlight. Measurements from the sensor are relayed to the 

Crestron control system, which adjusts indoor lighting to match 

outdoor lighting conditions.

Check the Box

Item

Qty

GLS-LCCT

1

Connector, 4-Pin, Male, White (P/N 2042613)

1

Connector, 4-Pin, Female, White (P/N 2042614)

1

Nut, 1/2 in.-14 (P/N 2047626)

1

O-ring, 1.64 in. OD, 1.36 in. ID, 50 Durometer (P/N 2052793)

1

Installation

The GLS-LCCT is designed to be mounted outdoors (on a roof) 

or indoors (beneath a skylight). When determining the mounting 

location, provide the GLS-LCCT with an unobstructed view of the 

sky. Use a 1/2 in. knockout (0.885 in. (22.5 mm) actual hole size) when 

mounting.

WARNING: 

To avoid personal injury and equipment damage, consider 

the following when mounting the GLS-LCCT outdoors:

• 

Secure the GLS-LCCT to an IP67 or better J-box to ensure that 

the enclosure remains waterproof.

• 

Use a CSP-LSP Lighting Strike Protector to prevent personal 

injury or damage to the control system and other devices on the 

Cresnet® network from a lighting strike.

• 

Mount the CSP-LSP inside the building at the point where the 

Cresnet network cable enters the building. The CSP-LSP must 

be properly grounded.

• 

For installation, wiring, and operation of the CSP-LSP,  

refer to the CSP-LSP Installation and Operation Guide at  

www.crestron.com/manuals

.

Install the GLS-LCCT:

1. 

Disconnect power to the system.

2. 

Seat the O-ring in the groove on the bottom of the sensor.

3. 

Thread the wire pigtail and the threaded nipple through the 

knockout. Ensure that the sensor sits flush with the J-box. 

4. 

Secure the sensor to the J-box using a 1/2 in.-14 NPT locknut. 

Tighten the locknut to ensure a proper seal with the J-box.

1/2 in. knockout 

(0.885 in. (22.5 mm) 

actual hole size)

IP67 or better box

1/2 in.-14 NPT nut

GLS-LCCT

5. 

Make the Cresnet network connections inside the box using the 

provided connectors.

6. 

Reconnect power to the system.

Wiring Diagram - Indoor Mounting Location

Cresnet to the 

control system

Wiring the 

GLS-LCCT inside 

the J-box.

Terminal  Wire Color
24: 

Red

Y: 

White

Z: 

Blue

G: 

Black

Wiring Diagram - Outdoor Mounting Location

Cresnet to the 

control system

Wiring the 

GLS-LCCT to the  

CSP-LSP inside 

the building 

space.

To a properly 

grounded point 

in the building.

Wiring the 

GLS-LCCT inside 

the IP67 or 

greater box.

Terminal  Wire Color
24: 

Red

Y: 

White

Z: 

Blue

G: 

Black

GLS-LCCT

Crestron SolarSync™ Outdoor Daylight and Color Temperature Sensor

Reviews: