Crestron
ST-PC
Dual AC Power Control
Module
Setup
Identity Code
Refer to the note on page 12 for a
definition of Viewport.
All equipment and user interfaces within the network require a unique identity code
(Net ID). These codes are two-digit hexadecimal numbers from 03 to FE. The Net
ID of each unit must match an ID code specified in the SIMPL Windows program.
Refer to “Setting the Net ID in Device Settings” on page 11 for details of the SIMPL
Windows procedure.
The Net ID of the ST-PC has been factory set to
2C
, The Net IDs of multiple ST-
PCs in the same system must be unique. Net IDs are changed from a personal
computer (PC) via the Crestron Viewport.
NOTE:
For detailed information on establishing communication between the PC
and control system, refer to “Communication Settings” on page 13. If
communication cannot be established, refer to the “Troubleshooting
Communications” section in the respective Operations Guide for the control system.
Use the following instructions to set or change the Net ID.
1. Ensure that the device requiring a Net ID change is the only unit connected
to the control system.
2. Open the Crestron Viewport.
3. From the Viewport menu, select
Functions | Set Network ID
. The software
checks the baud rate and then opens the "Set Network ID" window.
4. In the "Set Network ID" window, select the device requiring a Net ID
change from the
Current Network Devices
text window.
5. Select the new Net ID for the device from the
Choose the new network ID
for the selected device (Hex):
text box.
6. Click
Set ID
to initiate the change. This will display the "ID command has
been sent" window.
7. In the "Command Complete" window, click
OK
.
8. In
the
Current Network Devices
text window, verify the new Net ID code.
9. In the "Set Network ID" window, click
Close
.
NOTE:
The new Net ID code may also be verified by selecting
Diagnostic | Report
Network Devices
in the Viewport (alternately, select
F4
).
10. Repeat this procedure for each additional network device requiring a Net ID
change.
Hardware Hookup
Refer to the following hookup diagrams. Other than making the power connection
last, complete the connections in any order.
CAUTION:
Use only Crestron power supplies for Crestron equipment. Failure to do
so could cause equipment damage or void the Crestron warranty.
Operations Guide – DOC. 5708A
Dual AC Power Control Module: ST-PC
•
7