CellarSafe is fitted with an AC plug for convenience, however if permanent installation is required, it
should be wired to a dedicated AC spur fed from a circuit breaker, marked as the disconnecting
device for the CellarSafe.
The circuit breaker must comply with the relevant requirements of IEC 947-1and IEC 947-3. These
procedures ensure that the installation complies with the requirements EN 61010-1 (Low Voltage
Directive).
The repeater unit supplied with CellarSafe does not need specialist cabling. Each additional
repeater unit is supplied with a 9m cable as standard.