Crowmag control functions:

Step:

when the system is holding on a particular channel (ie the ‘Hold’ button has
been pressed), use the Step function to display and hold the next channel in
sequence. Also used to increase the Reading display in Channel Test mode
(section 7.4 of the standard Vortex manual). Hold Crowmag vertically to
activate.

Lamp test:

lights all display LED’s. Hold Crowmag horizontally to activate.

Inhibit:

places the appropriate input module into inhibit state. An LED indicates when
an input module is inhibited (‘Inh A’, ‘Inh B’, ‘Inh C’ LED’s). Hold Crowmag
vertically for input modules A and C, horizontally for input module B.

Warning: placing the system into inhibit state will isolate all output
functions: output/warning functions will therefore not operate in the
event of a gas or fire alarm. Care must be taken when using the inhibit
function to ensure the system does not remain permanently inhibited.
The system must be taken out of inhibit state once maintenance actions
have been performed.

Button functions:

Accept/Reset: silences the internal sounder and resets latched relays once an alarm state

has been cleared.

Hold:

forces the display to ‘Hold’ on a particular input channel. Also used to
decrease the Reading display in Channel Test mode (see Vortex manual
section7.4).

Run:

press either to restart cycling through the channels after HOLD has been
selected, or to end Channel Test mode.

Other display indications and functions are described below:

Feature

Description

System Fault LED

Yellow LED indicates a system fault. Specific system faults are
indicated on the Node controller module; refer to the Vortex manual
for more information.

Power Healthy LED

Yellow LED indicates system power status. Refer to section 6.4.2 of
the Vortex manual for more information.

Zone Inhibit LED’s

Yellow LED for each zone (A,B,C: Quad Input Modules). Indicates
that the zone (quad input module), or a channel in the zone, is
currently inhibited.

Hold LED

Green LED when continuously illuminated indicates that the HOLD
button has been used to hold the current channel.
When this LED flashes, it indicates "Jump on Alarm". The Channel
Reading now shows the channel (or the first of more than one
channel) that has gone into alarm.

Channel Test LED

Yellow LED when flashing indicates that the system is in Channel
Test mode. Refer to section 7.4 of the standard Vortex manual.

Units Indication LEDs

Indicates the units for the currently displayed channel.

Reading

The reading on the input device (detector) currently indicated by the
Channel display. The number is shown in red on a 7-segment display.
This should be read in conjunction with the 'units' indication. For the
use of this display in Channel Test mode, see section 7.4 of the
standard Vortex manual.

Channel Number

Green 7-segment display that normally displays the number of the
currently-displayed channel (detector). For the use of this display in

Summary of Contents for Vortex FP Compact

Page 1: ...Vortex FP Compact Flameproof Gas Detection Control System Installation and Operation Manual Issue 1 January 2013...

Page 2: ...described in this instruction manual has mains voltages applied to it Ensure correct safety procedures are adopted before working on the equipment The equipment described in this manual is designed f...

Page 3: ...TENTS 1 INTRODUCTION 3 1 1 SAFETY INFORMATION 3 1 2 PRODUCT DESCRIPTION 3 2 INSTALLATION 4 3 OPERATION MAINTENANCE 6 3 1 APPLYING POWER 6 3 2 COMMISSIONING 7 3 3 ROUTINE MAINTENANCE 7 3 4 VORTEX FP CO...

Page 4: ...ated control system designed for monitoring up to twelve gas detectors Three input channels may alternatively be used for monitoring conventional smoke or heat detectors or flame detectors Vortex FP C...

Page 5: ...the recognised standards of the appropriate authority in the country concerned and meet the electrical requirements of the field devices Field cables must be connected to the system using ATEX certifi...

Page 6: ...s Once the brackets are attached close the door and restrain using one fixing bolt before attempting to mount the cabinet 2 Lift the system in to place and secure via the mounting bracket fixing point...

Page 7: ...cted to the fused terminal A wiring diagram is shown on the next page If the equipment is permanently connected to a mains supply then a dedicated circuit breaker must be included in the installation...

Page 8: ...tallations are fully commissioned as soon as possible after installation Commissioning should include a full check of cabling and equipment functions as well as output functions Gas detectors must be...

Page 9: ...functions Vortex FP Compact must be completely de energised before the lid is opened local procedures must be adhered to when servicing equipment installed in a hazardous area 3 4 VORTEX FP COMPACT D...

Page 10: ...art cycling through the channels after HOLD has been selected or to end Channel Test mode Other display indications and functions are described below Feature Description System Fault LED Yellow LED in...

Page 11: ...ctions are shown below Warning access requires the Vortex FP Compact enclosure to be opened site procedures must be strictly adhered to before attempting to open the enclosure or to operate a powered...

Page 12: ...ftware can be used to inhibit individual channels Note Even in the inhibit condition the alarm LEDs on the display module are triggered if alarms occur 4 TECHNICAL SPECIFICATION Size 450mm x 330mm x 2...

Page 13: ...ter packaging of the returned goods Units returned to Crowcon as faulty and are subsequently found to be fault free or requiring service may be subject to a handling and carriage charge Warranty Discl...

Page 14: ...salesusa crowcon com Website www crowcon us European Office Crowcon Detection Instruments Ltd Vlambloem 129 3068JG Rotterdam Netherlands Tel 31 10 421 1232 Fax 31 10 421 0542 Email eu crowcon com Web...

Reviews: