background image

Vortex FP Compact Installation & Operation Manual

5

Issue 1, January 2013

cable. Other cables types may be used provided suitably certified cable glands are also
used.

Important note:

If a Vortex FP Compact system is to be connected to a control system in a

safe area (ie control room, plant room etc) it is strongly recommended that the Vortex RS-
485 function terminals are connected to an accessible point in the safe area. All Vortex
configurations, calibration and diagnostic functions can then be carried-out using the Vortex
PC software supplied with the system from the safe area without requiring the Flameproof
junction box to be opened. Refer to the Vortex manual for more details.

1. The fixing brackets/bolts are supplied with, but not fitted to the Vortex FP Compact

enclosure. To fit the brackets lay the Vortex FP Compact enclosure on a suitable
surface and raise onto one end. Remove the lid retaining bolts and carefully open the
lid of the enclosure. The fixing brackets should be secured to the enclosure using the
supplied retaining bolts/nuts.

Once the brackets are attached, close the door and restrain using one fixing bolt
before attempting to mount the cabinet.

2. Lift the system in to place and secure via the mounting bracket fixing points shown in

the diagram on the next page.

3. Ten M20 entries are provided for field cables. Connect the cables to the system

using certified Exd cable glands. Certified M20 plugs are fitted to five entries and can
be removed if necessary for additional cables. All spare cable entries must have Exd
certified plugs securely fitted.

4. Cable conductors should be connected to the Vortex modules and terminals as

shown in the Vortex manual (M07211).

Warning: power must not be applied until

the enclosure lid has been closed and securely tightened.

5. I.S. field devices (gas detectors and/or alarms) must be connected via safety barriers

mounted externally from the system, in accordance with their instructions.

Zener

Barriers must be grounded to a dedicated I.S. earth.

6. Once all cable connections have been made the lid should be closed and tightly

secured using the fixing bolts.

7. Connections to field devices (gas detectors, fire detectors etc) must be made

according to the instructions provided with each device.

System dimensions are shown on the following page.

Summary of Contents for Vortex FP Compact

Page 1: ...Vortex FP Compact Flameproof Gas Detection Control System Installation and Operation Manual Issue 1 January 2013...

Page 2: ...described in this instruction manual has mains voltages applied to it Ensure correct safety procedures are adopted before working on the equipment The equipment described in this manual is designed f...

Page 3: ...TENTS 1 INTRODUCTION 3 1 1 SAFETY INFORMATION 3 1 2 PRODUCT DESCRIPTION 3 2 INSTALLATION 4 3 OPERATION MAINTENANCE 6 3 1 APPLYING POWER 6 3 2 COMMISSIONING 7 3 3 ROUTINE MAINTENANCE 7 3 4 VORTEX FP CO...

Page 4: ...ated control system designed for monitoring up to twelve gas detectors Three input channels may alternatively be used for monitoring conventional smoke or heat detectors or flame detectors Vortex FP C...

Page 5: ...the recognised standards of the appropriate authority in the country concerned and meet the electrical requirements of the field devices Field cables must be connected to the system using ATEX certifi...

Page 6: ...s Once the brackets are attached close the door and restrain using one fixing bolt before attempting to mount the cabinet 2 Lift the system in to place and secure via the mounting bracket fixing point...

Page 7: ...cted to the fused terminal A wiring diagram is shown on the next page If the equipment is permanently connected to a mains supply then a dedicated circuit breaker must be included in the installation...

Page 8: ...tallations are fully commissioned as soon as possible after installation Commissioning should include a full check of cabling and equipment functions as well as output functions Gas detectors must be...

Page 9: ...functions Vortex FP Compact must be completely de energised before the lid is opened local procedures must be adhered to when servicing equipment installed in a hazardous area 3 4 VORTEX FP COMPACT D...

Page 10: ...art cycling through the channels after HOLD has been selected or to end Channel Test mode Other display indications and functions are described below Feature Description System Fault LED Yellow LED in...

Page 11: ...ctions are shown below Warning access requires the Vortex FP Compact enclosure to be opened site procedures must be strictly adhered to before attempting to open the enclosure or to operate a powered...

Page 12: ...ftware can be used to inhibit individual channels Note Even in the inhibit condition the alarm LEDs on the display module are triggered if alarms occur 4 TECHNICAL SPECIFICATION Size 450mm x 330mm x 2...

Page 13: ...ter packaging of the returned goods Units returned to Crowcon as faulty and are subsequently found to be fault free or requiring service may be subject to a handling and carriage charge Warranty Discl...

Page 14: ...salesusa crowcon com Website www crowcon us European Office Crowcon Detection Instruments Ltd Vlambloem 129 3068JG Rotterdam Netherlands Tel 31 10 421 1232 Fax 31 10 421 0542 Email eu crowcon com Web...

Reviews: