61
61
TABLE 12.1: PRESSURE SWITCH SETTINGS
MODEL
CROWN PN
APPROX. MAKE
SETTING (inches w.c.)
BREAK SETTING*
(inches w.c.)
CWD060 - CWD110
620039
1.21
1.16
CWD138 - CWD220
620040
1.40
1.35
CWD245
620041
1.45
1.40
*Settings shown are based on “plus tolerance” - actual setting may be lower.