background image

52

side panel installed in the previous step and secure with three #10 sheet metal screws.

5) Install the left side panel in the same manner as the right side.
6) Attach the front corners of the diverter panel to the side jacket panels using #10 sheet metal screws.
7) Install the horizontal (angle) jacket clips in the front edge of the side jacket panels. Slide this clip through the

rectangular slot that is about halfway up the front edge of the side jacket panels and secure with the 8-32 self
tapping screws provided.

8) Slip the Vertical Jacket Clip through the rectangular slot that is near the bottom of the front edge of the side jacket

panels. Secure with the 8-32 sheet metal screws provided.

9) Install the top jacket panel. Use #10 sheet metal screws to attach it to the rear jacket panel and the top-front corners

of the side panels.

10) Install the upper-front jacket panel. Insert the flange on the top of this panel under the top panel. Run two #10 sheet

metal screws into the horizontal jacket clips through the holes in the bottom of this panel.

11) Attach the door knobs to the Lower-Front Panel using 8-32 x 1/2 machine screws.
12) The labels have been applied at the factory.  Verify the location of the labels according to the list below:

a) Clearance Label - Located on the top jacket panel.
b) Lighting Instructions - Located on the lower left corner of the right side panel next to the gas manifold
c) Lowest Permissible Water Level Plate - Located next to the bottom water gauge tapping.
d) Blow Down Card - Located just above the "Lowest Permissible" Water Level Plate
e) Wiring Diagram - Located on the inside of the removable door
f)

"CROWN" Nameplate - Located on the top center of the outside of the removable door

g) Rating Plate - Located on the upper left of the right side panel

D. Gas Valve Installation

1) The gas valve assembly has been pre-piped with one half of a piping union and is to be connected to the other half

of the union located on the gas manifold.

2) Connect the pilot tubing from the pilot burner to the gas valve pilot tapping.
3) Connect the thermocouple lead to the gas valve (standing pilot boilers only).

E. Control and Trim Installation

  

(Refer to Figure A3 for Tapping Locations)

1) Install the tankless heater or blank cover plate on the opening on the right side of the heat exchanger using the

gasket and 3/8 bolts provided.

2) Install the high limit well in the tapping in the tankless heater or cover plate.
3) Mount the limit control (L8148E or L8124E) onto the control well. Be sure that the temperature sensing bulb is

bottomed out in the well. Tighten the screw on the bottom of the control so that it is securely clamped onto the well.

4) Install a 1/2 x 1/4 bushing and the tridicator gauge into tapping “C”.  Tighten with wrench applied to the square

shank on the back of the gauge. Do not apply pressure on the gauge case since this may ruin the calibration of the
gauge.

5) Install relief valve (spindle must be in vertical position) into tapping “H” on the boiler left side (See Figure 1 in the

installation manual) using the ¾” NPT nipples and elbow supplied.  Pipe the discharge of the safety relief valve to a
location where water or steam will not create a hazard or cause property damage if the valve opens.  The end of the
discharge pipe must terminate in an unthreaded pipe.  The safety valve discharge piping must be in an area where it
is not likely to become plugged by debris or subjected to freezing.

6) Install the 1-1/2 return piping and circulator in tapping “D”. See Section VIII System Piping in the installation

manual for instructions on completing the piping of this boiler.

51

Summary of Contents for CWI Series

Page 1: ...INSTRUCTIONS These instructions must be affixed on or adjacent to the boiler WARNING Improper installation adjustment alteration service or maintenance can cause property damage injury or loss of lif...

Page 2: ...oduct Description The CWI series boilers are low pressure cast iron gas fired hot water boilers designed for use in closed hot water heating systems These boilers are Category I draft diverter equippe...

Page 3: ...41 202 81 1 83 2 3 75 4 75 29 30 40 7 16 7 18 8 CWI276 9 276 232 81 4 83 2 4 00 5 25 32 1 4 30 40 7 16 8 21 0 CWI310 10 310 259 4 00 5 25 35 1 2 30 45 7 16 8 23 2 CWI345 11 345 288 4 00 5 25 38 3 4 30...

Page 4: ...tural or LP The CWI345 and CWI379 may only be used with natural gas 5 Boilers installed at altitudes above 2000 ft may require different burners and main burner orifice than those at sea level Make su...

Page 5: ...dilution Provisions for combustion ventilation and flue gas dilution air for gas utilization equipment vented by natural draft must be made in accordance with local building codes or in absence of su...

Page 6: ...the ceiling The top edge of the upper opening must be within 12 of the ceiling and the bottom edge of the lower opening must be within 12 of the floor Figure3 Each opening must have a free area of 1...

Page 7: ...7 6 FIGURE4 ALLAIRFROMOUTDOORS VENTILATED CRAWL SPACE AND ATTIC FIGURE5 ALLAIRFROMOUTDOORS VIA VENTILATED ATTIC FIGURE3 BOILERINSTALLEDINCONFINEDSPACE ALL AIR FROM INSIDE...

Page 8: ...8 FIGURE6 ALLAIRFROMOUTDOORS USING OPENINGSINTOBOILERROOM FIGURE7 ALLAIRFROMOUTDOORS USING HORIZONTAL DUCTS INTO BOILER ROOM 7...

Page 9: ...ctive cases CWI series boilers may be vented into an exterior ceramic lined masonry chimney See the National Fuel Gas Code for information on when exterior chimneys may be used An exterior masonry chi...

Page 10: ...e following steps shall be followed with each appliance remaining connected to the common venting system placed in operation while the other appliances remaining connected to the common venting system...

Page 11: ...11 10 FIGURE8 CWI BOILERTYPICALVENTSYSTEM INSTALLATION AND COMPONENTS FIGURE 9 VENTDAMPERINSTALLATIONDETAILS...

Page 12: ...controls Install a manual shut off valve outside the jacket and ground joint union as shown The boiler and its gas connection must be leak tested before placing the boiler in operation When doing thi...

Page 13: ...tor Required Although the circulator is shipped on the boiler return it can be installed on the boiler supply If the circulator is moved to the supply it should be positioned just downstream of the ex...

Page 14: ...ystems The piping shown in Figure 13 will minimize the amount of time that the boiler operates with return temperatures below 120 F on these systems A bypass is installed as shown to divert some suppl...

Page 15: ...15 14 FIGURE12 INDIRECTWATERHEATER BOILERSIDEPIPING FIGURE11 STANDARDBOILERPIPING...

Page 16: ...g for a gravity hot water boiler The circulator 1 1 2 x 2 bushings and 1 1 2 piping are removed and the system piping is run directly to the 2 supply and return tappings on the boiler If isolation val...

Page 17: ...17 FIGURE15 BOILERPIPINGWITHCHILLER FIGURE14 ISOLATIONOFBOILERFROMSYSTEMWITHAHEATEXCHANGER 16...

Page 18: ...ting range of approximately 110 to 130F Follow the manufacturer s instructions for installing this valve Usually a heat trap will be required between the coil and the hot connection on the mixing valv...

Page 19: ...boiler Install unions anywhere in the tankless heater piping that will facilitate removal of the heater 7 Backflow Preventer Required in Massachusetts If required by local codes install a backflow pr...

Page 20: ...spots near any heat source or in direct sunlight cold spots outside walls walls adjacent to unheated areas locations subject to drafts Provide Class II circuit between thermostat and boiler Connect t...

Page 21: ...ESS IS REPLACED WITH JUMPER PLUG TH TR ROBERTSHAW 7000DERHC GAS VALVE CWI379 HONEYWELL VR8204 VR8304 SERIES GAS VALVES CWI069 345 2 NOTE 2 2 VENT DAMPER REQUIRED ON ALL BOILERS EXCEPT CWI310 CWI379 WH...

Page 22: ...used for other 24 volt zone valves as long as they are equipped with end switches Do not attempt to use the transformer on the limit control to power the zone valves use a separate transformer Up to...

Page 23: ...23 22 FIGURE23 ZONEWIRINGUSINGHONEYWELLV8043FZONEVALVES FACTORYWIRINGNOTSHOWN SEE FIGURES18 21 FIGURE22 CIRCULATORZONEWIRINGUSINGHONEYWELLR845As FACTORYBOILERWIRING NOTSHOWN SEE FIGURES 18 21...

Page 24: ...ition the damper will close 2 If the boiler water temperature is less than the low limit setting minus the differential setting terminals R and B in the L8124E are made through the low limit switch Th...

Page 25: ...mperature is less than the low limit setting minus the differential setting terminals R and B in the L8124E are made through the low limit switch The low limit switching action is SPDT with R being co...

Page 26: ...THE BOILER UNDERWENT THE TESTS SPECIFIED IN Z21 13 25 Safety Control Operation Standing Pilot and Intermittent Ignition High Limit Interrupts main burner operation when the supply water temperature e...

Page 27: ...26 No yellow tipping should be present however intermittent flecks of yellow and orange in theflamearenormal 12 Check entire gas train for leaks using soap and water or other approved leak detection...

Page 28: ...ct a manometer to the manifold outlet pressure tap on the gas valve see Figures 27 and 28 d Read the manifold pressure It should be set at NaturalGas LPGas Manifold Press inches w c 3 5 10 0 e If a ma...

Page 29: ...ncrease to hi limit setting The burners should shut down and the circulator continue running For standing pilot boiler models pilot burner should remain lit but the main burners should stop firing For...

Page 30: ...light pilot burner with a match After about one minute release reset button Pilot should remain lit If it goes out turn gas control knob clockwise to OFF To relight repeat steps 5 9 If button does no...

Page 31: ...old the Knob while you light pilot burner with a match After about one minute release reset button Pilot should remain lit If it goes out turn gas control knob clockwise to OFF To relight repeat steps...

Page 32: ...all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do try to light the pilot by hand not 5 Remove front access panel 6 Rotat...

Page 33: ...lowest setting 3 Turn off all electric power to the appliance 4 This appliance is equipped with an ignition device which automatically lights the pilot Do try to light the pilot by hand not 5 Remove f...

Page 34: ...ANDVR8304 INTERMITTENT IGNITION FIGURE 27a GASVALVEDETAIL HONEYWELLVR8200ORVR8300 STANDINGPILOT FIGURE 27b GASVALVEDETAIL ROBERTSHAW 7000ERHCANDHONEYWELLV8295 STANDINGPILOT FIGURE 28b GASVALVEDETAIL R...

Page 35: ...ounding strap The ideal gap between the electrode and the ground strap is 1 8 Inspect the porcelain for cracks or other deterioration Replace pilot assembly if deterioration is found 6 Inspect the com...

Page 36: ...the pilot main burner in its original location 16 Replace the blocked vent switch 17 Reconnect the damper and vent system WARNING SOOT DEPOSITS IN THE FLUE PASSAGES ARE A SIGN THAT THE BOILER MAY BE...

Page 37: ...f voltage is present the damper is defective or there is an obstruction in the path of the damper blade If no voltage is present there is either a loose connection in the damper harness or the limit c...

Page 38: ...d sw itch w iring Defective t stat or zone valve end sw itch T stat or zone system misw ired consult t stat or zone valve manufacturer s instructions Vent damper open 24 volts across B and R limit sw...

Page 39: ...raft Inadequate combustion air supply in boiler room Y N N Y Y 24 volts across rollout sw itch Loose electrical connection in 24 volt w iring betw eenB1 or B2 and gas valve or module Rollout sw itch o...

Page 40: ...itch and B2 Y Refer to standing pilot or intermittent ignition troubleshooting chart page 41 or 42 START Defective damper Defective damper harness Loose damper harness connection Obstruction in path...

Page 41: ...nt T stat or zone system misw ired consult t stat or zone valve manufacturer s instructions N Do burner and circulator shut dow n at end of call for heat END Pull w ire off of T terminal on aquastat D...

Page 42: ...orifice partially plugged Y N N Y N Turn control on gas valve to ON Y END Defective gas valve Y START 24 VOLTS PRESENT ACROSS TH AND TR ON GAS VALVE BUT MAIN BURNERS DO NOT LIGHT Ensure knob on gas v...

Page 43: ...rcelain cracked Pilot flame not covering gap between electrode and grounding strap Low gas pressure at gas valve inlet Defective S8600 module Main burner lights N Y 24VAC across terminals 1 2 on S8600...

Page 44: ...1 2 SELF TAPPING SCREW 900100 20 ea 20 ea 20 ea 20 ea 21 ea 21 ea 21 ea 21 ea 25 ea 25 ea 11 1 2 x 2 SEALING STRIP 900146 3 7 ft 4 2 ft 4 8 ft 5 3 ft 5 9 ft 6 4 ft 7 0 ft 7 5 ft 8 0 ft 8 5 ft 12 ROLL...

Page 45: ...45 44...

Page 46: ...0 043 900041 900041 900041 49 35 1600 392449 50 35 1650 392449 4 51 51 51a 51 51a 61 40mm BURNER LESS PILOT BRACKET 150541 1 ea 2 ea 3 ea 4 ea 5 ea 6 ea 7 ea 8 ea 62 MANIFOLD 40mm BURNERS 1 ea 701253...

Page 47: ...47 46...

Page 48: ...3 96 033 96 035 96 035 96 036 96 036 89 3 4 SHORT WELL LESS COIL BOILERS 35 1010 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 1 ea 89 3 4 LONG WELL WITH COIL BOILERS 35 1020 1 ea 1 ea 1 ea 1 ea 1 ea 1...

Page 49: ...49 48...

Page 50: ...e care not to disturb the ceramic fiber gasket 2 Once the heat exchanger has been placed on the base inspect the gasket for proper seal Repair or replace gasket if necessary 3 Secure the heat exchange...

Page 51: ...51 50 FIGUREA1 BASE HEATEXCHANGER FLUE COLLECTORASSEMBLY...

Page 52: ...emovable door g Rating Plate Located on the upper left of the right side panel D GasValveInstallation 1 The gas valve assembly has been pre piped with one half of a piping union and is to be connected...

Page 53: ...53 52 FIGUREA2 JACKETINSTALLATION...

Page 54: ...ide redundancy This valve should be factory pre wired to the 7000ERHC with one black lead connected to the TH terminal and the other black lead connected to the TR terminal on the 7000ERHC gas valve 5...

Page 55: ...55 54 FIGUREA3 TAPPING LOCATIONS SEE TEXT FOR TAPPING USES...

Page 56: ...56 Tel 215 535 8900 Fax 215 535 9736 www crownboiler com Manufacturer of Hydronic Heating Products P O Box 14818 3633 I Street Philadelphia PA 19134...

Reviews: