Issue 1
15
Section 4
Maintenance
4.1 servicing
Servicing should be carried out annually by a gas safe registered engineer ,the service should
include changing the ODS pilot if warranty is to be extended if not thoroughly clean , also the
chimney /flue should be checked and the appliance removed to check for debris in the fireplace
opening ,a smoke test must be carried out to check for up draught and no leakage in the flue
check the condition of the fuel pieces and if necessary replace with Genuine replacements from
crystal fires
after servicing a soundness test and working pressure should be tested and a spillage test
1. Removal of fuel pieces
remove trims and fire front and remove screws holding glass in place ,remove the glass the fuel
pieces can then be removed and placed carefully so not to get damaged
Replace as per instructions
replace glass by inserting glass into bar at bottom and push into place whilst holding glass place
the outer frame into place and put 8 screws in , only tighten when glass is safe all screws in by
hand
2. replacement of gas control and pilot (Manual and remote)
Remove glass & fuel set as above
isolate appliance from gas supply and disconnect from inlet elbow
remove securing screws holding fire tray in place , the fire tray can now be removed
remove control knob (manual) and disconnect gas connections to gas valve including the pilot
connection also disconnect the thermo couple nut by unscrewing or remote pull off the leads
making a note of position ,
remove screws on remote and locknut on manual the valve is then free
to remove pilot remove screws holding it in place
Re assemble in revers order
3.replacement of injector
remove fuel and glass as per
1.
repeat
2.
to remove gas control
the injector can now be removed by unscrewing locknut holding it in place and it can be removed
and cleaned or replaced (only replace with exactly the same )
RE assemble in reverse order ensuring all nuts fully tight and remote control connections secure
Turn on gas supply, check for soundness and re-commission the fire
perform spillage test & check all joints are sound