Sensor-settings
PI 500
Seite
44
von
93
7.3.2.1.2.9.9 Settings ZeroPoint or Low Flow Cut off for VA 5xx
Main menu
Settings
Sensor settings
C1
More-Settings
Zeropoint
2.045
2.045
With these function following adjustments for
the sensor VA 5xx could be done:
Zeropoint:
When, without flow, the installed sensor shows
already a flow value of > 0 m³/h herewith the
zero point of the characteristic could be reset
Cutoff:
With the low-flow cut off activated, the flow
below the defined "LowFlow Cut off" value will
be displayed as 0 m³/h and not added to the
consumption counter.
For Zero Point the text field “ ZeroPoint” to
enter and insert the displayed actual flow, here
2.045
For inserting low flow cutoff value activate the
text field “CutOff” and insert the required
value, here 10.
With the Reset” button all entries could be set
back to zero.
Inputs / changes to be confirmed with
“OK”
button. Return to main menu with
“Back”.