Proximity Readers
Installation Guide
36
CSI Readers
Proximity Readers
CSI provides eight models of proximity readers for indoor or outdoor uses. The read
ranges vary by model from 0–4" to 0–15" (0–10 cm to 0–38 cm). The standard data
format for these readers is Wiegand. These readers provide an LED function, red for
access denied, and green for access granted.
PR-110 and PR-112
The PR-110 proximity reader is an indoor Standard Reader. You can mount it on any
surface, including metal, or concealed behind most non-metallic building materials. You
may also mount it against a metal door or window frame. The read range is 0–6" (0–15
cm) with the PC-121 Card. The PR-112 is the outdoor version of this reader. Use the
following steps to install the field output cables. Directly connect the wires to the DPU-
7920 at the TB3 or TB4 terminals using the following steps (see
).
1.
Connect the white wire (
Data-1
) to terminal 3.
2.
The blue wire (Beeper) is not connected.
3.
Connect the green wire (
Data-0
) to terminal 5.
4.
Connect the brown wire (LED) to terminal 6 for Red LED operation.
5.
Connect the orange wire (LED) to terminal 7 for Green LED operation
6.
Connect the black wire (Ground) to terminal 8.
7.
Connect the shield and earth ground to terminal 2.
8.
Connect the positive lead of the 12 VDC linear power supply to the red wire at the
PR-110 or PR-112.
9.
Connect the negative lead of the 12 VDC linear power supply to terminal 8.
Note:
You should always locate the linear power supply as close to the reader as physically possibly
to ensure maximum read ranges and placement separation.
PR-503 and PR-505
The PR-503 proximity reader is an indoor/outdoor mullion reader. You can mount it on
any surface, including metal, or concealed behind most non-metallic building materials.
You may also mount it against a metal door or window frame. The read range is 0–4"
(0–10 cm) with the PC-121 Card. The PR-505 is an indoor wall switch reader, and
mounts similarly to the PR-105. Use the following steps to install the field output cables
to a breakout box. Directly connect the wires to the DPU-7920 at the TB3 or TB4 termi-
nals using the following steps.
1.
Connect the white wire (
Data-1
) to terminal 3.
2.
The blue wire (Beeper) is not connected.