Impedo
DUO
User Guide
65
5.7.3.2
Health Shutdown
Figure 27: Health-Manager configuration
Health-Manager periodically checks the system health. The battery charge level and
system temperature is shown on the OLED display. Health-Manager will shut down
the instrument to protect it from damage if the system temperature drops below
0 ⁰C or rises above 75 ⁰C. Health-Manager will shut down the instrument to protect
the battery from damage if the battery charge level drops below 0 %. Uncheck the
Enable
checkbox (see Figure 27) to instruct Health-Manager to disregard the system
health.
Disabling Health-Manager may cause permanent damage to the
instrument should a health-based shutdown be indicated
5.7.3.3
Time
Figure 28: Time-Master configuration
The Impedo Duo will not record any PQ data unless it has valid time. Time-Master
manages this aspect of the instrument. It automatically determines the best time
source. It will use the following sources in order of preference: GPS, Network time,
internal clock. Automatic time source selection can be disabled by setting the time
source explicitly to either GPS or NTP.