Impedo
DUO
User Guide
94
6.2.4
Voltage connections
6.2.4.1
Single phase connection
Always connect the safety earth terminal located on the power
connector first!
Table 10: VT circuit connection layout for single phase connection
Terminal
Legend
110V VT Circuit or 400V/550V Star (4-wire) Systems
1.
V
1
Phase Voltage
2.
V
2
Open
3.
V
3
Open
4.
V
com
Neutral
5.
V
4+
Earth
6.
V
4-
Neutral
Connect the phase Voltage to Voltage Inputs 1 as shown in Figure 61.
Connect Neutral (400 V systems) or the star-point (110 V VT circuits) to V
com
.
The fourth voltage input may be used to measure Neutral-Earth voltage.
Figure 61: Impedo DUO single-phase connection
Phase
1
Phase
4
Ref
Phase
4
Neutral