7
CTC 380 S
General information
3-stroke oil-heating boiler CTC 380 S
Model
18
22
27
33
Rated output
kW
18,3
22
27,3
33,9
Rated input
kW
19,6
23,7
29,2
36,1
Oil supply
kg/h
1,65
2,0
2,46
3,05
Flue gas mass low
g/s
8,2
9,9
12,2
14,7
Boiler resistance
mbar
0,07
0,10
0,14
0,21
Boiler water resistance ( Δ 20K)
mbar
2,0
2,0
3,0
3,0
Flue gas losses *
%
5,49
5,19
5,61
5,7
Radiation losses *
% / W
1,11 / 216
1,11 / 216
0,79 / 215
0,6 / 215
Boiler eficiency
%
93,4
93,7
93,6
93,7
Flue gas temperature *
°C
138
136
146
160
Boiler eficiency at 70 °C
%
93,8
94
94
94,1
Flue gas temperature 70 °C
°C
130
128
138
152
Max. Operation pressure boiler (PS)
Bar
3
3
3
3
Max. Operation temperature boiler
°C
110
110
110
110
Water content
l
98,5
98,5
92
92
Weight
kg
197
197
200,5
210
Number of turbulators
Pcs.
6
6
9
9
Turbulator model
21/45
27/45
27/45
21/45
Electrical data
230V 1N~
230V 1N~
230V 1N~
230V 1N~
1. Technical information
1.1
Technical data
3-stroke oil-heating boiler CTC 380 S
Model
40
50
63
Rated output
kW
39,7
51,2
61,6
Rated input
kW
42,7
55,1
66,9
Oil supply
kg/h
3,6
4,65
5,65
Flue gas mass low
g/s
17,1
23,7
29,7
Boiler resistance
mbar
0,4
0,29
0,5
Boiler water resistance ( Δ 20K)
mbar
5,0
8,0
9,0
Flue gas losses
%
5,7
6,75
7,61
Radiation losses
% / W
0,6 / 215
0,45 / 249
Boiler eficiency
%
1,11 / 216
Flue gas temperature *
°C
Boiler eficiency at 70 °C
%
Flue gas temperature 70 °C
°C
Max. Operation pressure boiler (PS)
Bar
Max. Operation temperature boiler
°C
Water content
l
Weight
kg
Number of turbulators
Pcs.
Turbulator model
Electrical data
230V 1N~
* According to
EN 303-3
Summary of Contents for 380 S 18
Page 2: ......
Page 42: ...42 CTC 380 S General information ...