      Disconnect the power supply before 

beginning installation to prevent electric shock 

or equipment damage.

      All wiring must comply with local codes 

and ordinances.

To wire and mount the thermostat:

1.  Remove cover from thermostat base by 

gripping the base in one hand.  Use the 

other hand to pull gently at the top or 

bottom of the cover.

2.  Carefully remove the protective packing.

3.  Loosen the 4 screws holding the 

thermostat to the sub-base, then separate 

them.  Refer to Figure 1.

4.  Pull wires through opening near center 

of sub-base and connect wires beneath 

terminal screws (See figure 2-5 for typical 

wiring for each application, Also refer 

to the following subsections for special 

system configurations).

5.  Push excess wiring into wall and plug 

hole with fire-resistant material (such as 

fiberglass insulation) to prevent drafts 

from affecting thermostat operation.

6.  Position sub-base over hole in wall and 

mark mounting locations.  Use any existing 

mounting holes if possible.

7.  If the mounting screws will be going into 

drywall only, then drill 3/16” mounting 

holes for use with the included plastic 

anchors.

8.  Fasten sub-base loosely to wall with two 

mounting screws.  Place a level on the 

raised, flat surface near the bottom of the 

sub-base, adjust until level, then tighten 

the mounting screws.  (Refer to Figure 2.)

An incorrectly leveled thermostat 

will cause the temperature control to 

deviate from the setpoint.

ATTACH SUB-BASE TO WALL

Electric Heat Furnaces 

(Single Transformer Systems only)

      The sub-base, as supplied, may not operate 

the fan correctly. If both the heating and the 

cooling system must operate the fan relay, 

remove the factory-installed jumper wire 

from the 

Y

 terminal and connect it to the 

terminal. The fan should now cycle when the 

thermostat calls for either heat or cool.

Two-Transformer Systems

If two transformers are used, they must 

be in phase. Failure to do so may result 

in personal injury and/or property 

damage.

      NOTE: 

Wire color does not indicate 

polarity.  Polarity is obtained from an 

oscilloscope or voltmeter.

Remove jumper between RC and RH terminals 

for two transformer systems.

Heat Pump Applications

      This sub-base 

WILL NOT 

provide multi-

stage heating or cooling operation. For 

single stage heat pump applications, install 

a short jumper wire across terminals 

and 

Y

. If the old thermostat has a terminal that 

is continuously energized, disconnect the 

wire from the old thermostat’s terminal and 

connect it 

either

 to the: 1) 

B

 terminal, if the 

reversing valve is energized on a call for heat; 

or

 to the 2) 

O

 terminal, if the reversing valve is 

energized on a call for cool. If the system heats 

on a call for cool, or vice versa, this wire has 

been connected to the wrong terminal.

      NOTE: RH 

and 

RC

 must be jumpered for 

single transformer heat pump systems.

Special Application Terminals

      The 

B

 and 

terminals can provide 

switching for special functions other than heat 

pump operation. When the system switch is in 

the 

HEAT

 position, the 

terminal is energized. 

When the system switch is in the 

COOL

 

position, the 

O

 terminal is energized.

SPECIAL APPLICATIONS

1.  Attach thermostat base to sub-base, being 

sure that 4 captive screws are tightnened 

snugly, since they serve as electrical 

connections between thermostat and sub-

base.

2.  Snap cover on thermostat and set switches 

and temperature lever to desired setpoint 

3.  Turn on power to the system.

ATTACH THERMOSTAT TO SUB-BASE

TYPICAL WIRING DIAGRAMS

LEVELING
SURFACES

FIG.2.  THERMOSTAT SUB-BASE

FACTORY

INSTALLED

JUMPER

WIRE

YELLOW

JUMPER

FIG. 3.  SINGLE TRANSFORMER H/C SYSTEM

For electric heat-fan to cycle with either heat or cool, move yellow jumper from Y terminal to A 

terminal (see dotted line at terminal A in illustration.)

FIG. 5.  SINGLE TRANSFORMER, SINGLE STAGE HEAT PUMP SYSTEM

Install jumper between W and Y terminals (see illustration.)

FIG. 1 ATTACH THERMOSTAT TO SUB-BASE

FIG. 4.  TWO TRANSFORMER H/C SYSTEM

    

    

FIELD

INSTALLED

JUMPER

WIRE

FACTORY

INSTALLED

JUMPER WIRE

41630-01  4/22/2003