25
CTC EcoLogic M/L
ºC
ºC
Summer-time operation
All properties have internal heat gains (lamps, oven,
body heat, etc.), which means that the heating can be
switched off when the outdoor temperature is lower
than the desired room temperature. The better insulated
the house is, the earlier the heating from the heat pump
can be switched off.
The example shows the product set at the default value
of 18°C. This value,
"Heating off, outside"
, can be
changed in the "Advanced / Settings / Heat System"
menu.
In systems with a radiator pump, the radiator pump
stops when the heat is switched off. The heating starts
up automatically when it is required again.
Automatic or remote-controlled summer period
The factory setting causes "summer" to commence
automatically at 18ºC, as "Heating mode" is set to
"Auto".
Heating, mode
Auto (Auto/On/Off)
Auto
means automatic.
On
means that the heating is on. For systems with
a mixing valve and a radiator pump, the mixing valve
operates to the primary flow setpoint and the radiator
pump is on.
Off
means that the heating is switched off. For systems
with a radiator pump, the radiator pump is switched off.
Heating, ext. mode
- (- /Auto/On/Off)
Facility for remote control of whether the heating is to be
on or off.
Auto
means automatic.
On
means that the heating is on. For systems with
a mixing valve and a radiator pump, the mixing valve
operates to the primary flow setpoint and the radiator
pump is on.
Off
means that the heating is switched off. For systems
with a radiator pump, the radiator pump is switched off.
- No selection means no function when activated.
Heating up
Heating up
Outside Temperature
Heating off, out
Primary Flow Temperature
Heating
switched
off