73
CTC EcoLogic M/L
Primary flow temp at o20 °C** 20 (2...20)
Specify the temperature of the cooling flow at an
outdoor temperature of 20°C.
Recommended values depending on system:
• Radiator/Underfloor heating = 20 °C
• Fan convector = 20 °C
Primary flow temp at o40 °C** 20 (2...20)
Specify the temperature of the cooling flow at an
outdoor temperature of 40 °C.
Recommended values depending on system:
• Radiator/Underfloor heating = 20 °C
• Fan convector = 20 °C
Primary flow diff. at o20 °C**
2 (1...10)
Specify how many degrees of difference is permitted
between the primary flow and return temperature of the
cooling flow at an outdoor temperature of 20 °C.
Primary flow diff. at o40 °C**
2 (1...10)
Specify how many degrees of difference is permitted
between the primary flow and return temperature of the
cooling flow at an outdoor temperature of 40 °C.
SmartGrid Low price °C
1 (Off, 1...5)
The menu bar is displayed if SmartGrid have been
defined in the “Installer/Define/Remote Control” menu.
Read more in the “Remote Control/SmartGrid” section
of the “Installer/Define” chapter.
SmartGrid Overcapacity °C
2 (Off, 1...5)
The menu bar is displayed if SmartGrid have been
defined in the “Installer/Define/Remote Control” menu.
Read more in the “Remote Control/SmartGrid” section
of the “Installer/Define” chapter.
Ext. block., cooling
Yes (Yes/No)
Blocking cooling can be remote controlled remotely. For
example, the function can be used to turn off cooling
with the help of a humidity sensor when there is a risk of
condensation.
This menu bar is displayed if the criteria below are met:
• a remote control input has been defined for the
“Block cooling” function.
• a normal mode (Normally Open (NO) or Normally
Closed (NC)) for the external control signal has
been defined on the menu bar “Block cooling ext.
config.” in the “Installer/Define/Cooling” menu.
Read more in the “Def. Remote Control” section of the
“Installer / Define” chapter.
Block cooling, schedule
This menu is used to schedule the weekday periods
during which cooling should be blocked. This schedule
is repeated every week.
This menu bar is displayed if a weekly program has
been defined for the “Block Cooling” function, in the
“Installer / Define / Remote Control” menu.
For more information, refer to:
• chapter “Weekly Program” for schedule setting.
• section “Def. Remote Control” of the
“Installer / Define” chapter for defining the remote
control function.
**The menu bar is only displayed if active cooling has
been defined in the “Installer /Define/Cooling” menu.