Menu: "Installer/Settings/Pool".
Activate this function via an external control signal or a weekly
program.
Menu: "Installer / Define / Pool".
A mode for the external control signal ("Normally Open (NO)" or
"Normally Closed (NC)") is defined in the "Installer/Define/Pool"
menu.
Block Pool
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
This function is used to block pool heating.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define / Pool" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC)).
In the "Installer/Settings/Pool" menu:
• set the "remote control mode" ("On") in the
"Blocking Pool" row.
Access function scheduling from the "Block. pool,
schedule" row.
For more information, refer to the "Pool" section in the
"Installer/Settings" chapter.
Tariff EL
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
This function is used to block the electric heater during
periods when the electricity rate is higher.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer/Settings/Additional Heat" menu:
• set "remote control mode" ("Yes") in the "Tariff EL"
row.
Access function scheduling from the "Tariff EL" row.
For more information, refer to the "Additional Heat/Tariff
EL" section in the "Installer/Settings" chapter.
Round circulation
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
Round circulation is equipment which an electricity
supplier can fit in order to disconnect, for a short period
of time, equipment which draws high current. The
compressor and electrical output are blocked when
round circulation is active.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer/Settings” menu:
• Access function scheduling from the "Round
circulation" row.
For more information, refer to the "Round circulation"
section in the "Installer/Settings" chapter.
Menu: "Installer/Settings/Additional Heat".
Setting "Tariff EL" via an external control signal or a weekly
program.
Menu: "Installer/Settings”. Setting a "Round circulation" weekly
program.