85
CTC EcoLogic M/L
K22 (SG A)
K23 (SG B)
Function
Open
Open
Normal
Open
Closed
Low price
Closed
Closed
Overcapacity
Closed
Open
Blocking
*The number of possible heating circuits or heat pumps
that can be connected to the system varies depending
on the control system.
Menu: "Installer/Define/Heat Pump".
A mode for the external control signal ("Normally Open (NO)" or
"Normally Closed (NC)") is defined for "Tariff HP ext. config.".
The weekly program is set to start at 22:30, weekdays.
SmartGrid functions are enabled by activating the
SmartGrid inputs in different ways according to the table
on the right.
To enable the SmartGrid function "SG Low Price"
as shown in the example, terminal block K23 must
have power while terminal block K22 should remain
unchanged.
The pool temperature increase that will apply when
"SG Low Price" is activated is set in the "Pool Settings"
menu, as shown in the example.
Alternatively, a weekly program can be set up for
periodic SmartGrid activation. Refer to the "Weekly
Program" chapter for more information.
Vent. Reduced/Vent. Normal/Vent. Forced /
Vent. Custom/Vent. Absent
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
When there is a signal in the respective ventilation
function’s remote control input, the selected ventilation
mode will start and be active for half an hour.
In the "Installer / Define/Remote Control" menu:
• specify and "Input" for current ventilation
functions.
Click the Ventilation symbol in the start menu to access
the "Ventilation" menu, where ventilation settings can be
made. The weekly program can also be accessed from
there. However, a weekly program cannot be specified
for the "Vent. Away" ventilation mode.
For more information, please refer to the CTC EcoVent
ventilation product manual.
HP Tariff (1-*)
(Off/ K22-K25 /Channel 1A-7B / BMS DI0-7)
This function is used to block the heat pump during
periods when the electricity rate is higher.
In the "Installer / Define/Remote Control" menu:
• specify an "Input" for the remote control function.
In the "Installer / Define/Heat Pump" menu:
• configure the normal mode for the external control
signal (Normally Open (NO)/Normally Closed (NC))
in the "Tariff HP ext. config." row.
In the "Installer/Settings/Heat Pump/Heat Pump (1-)*"
menu:
• set "Tariff HP" ("On").
For more information, refer to the "Heating Pump"
section in the "Installer/Settings" chapter.