background image

Series 4 Module User Guide—North America 

| Page 8 of 17 

 

 
 
 

4.2

 

Module Orientation 

 

PV performance modeling software should be used to determine the optimum orientation and tilt angle for each location. 

 

For tilted free-field applications or single-axis tracker applications where there is row to row shading, modules shall be 
installed in landscape orientation. 

 

 

4.3

 

Module Shading Considerations 

 

To  maximize  performance,  modules  should  be  located  in  an  area  that  receives  direct  sunlight  from  mid-morning  to  mid-
afternoon (typically 9:00 a.m. to 3:00 p.m.). Installation must avoid locating the modules where shadows may be caused by 
buildings, trees, etc. 

 

Specific shading patterns can cause damage to module cells due to the creation of localized areas of reverse bias. Reverse bias 
is generated by one or more series-connected cells being shaded while the rest of the cells are fully illuminated. When shading 
geometry is suitable for damage to occur, it can happen in very short durations (seconds to minutes) and under a wide range 
of irradiance (as low as 160 W/m

2

). An example of prohibited shading orientation is presented below. 

 

 
 
 
 
 
 

 

There is no risk of module damage due  to “row-to-row” shading in landscape orientation. There is also no risk if shading 
occurs while modules are in open circuit conditions or no risk from diffuse shading for objects greater than 2 meters or 7 
feet. 

 

There is a low risk of module damage due to shading from walking or standing in front of operating modules or from parking or 
driving  vehicles in  front  of operating modules during illuminated times. Best practice  is to  stay close to the back side of the 
adjacent rack as one travels down a row of operating modules. 

 

Instances of shading that will lead to a voided warranty include the High Risk items listed below. 

 

High Risk (Prohibited) Shading 

 

1.

 

Resting or adhering slender objects (tools, brooms, clothing, wires, tape) on sunny side of operating modules, or when 
nearer than ~5-7 feet above operating modules, especially when shadow oriented parallel to cells. 

 
2.

 

Fixed objects within ~5-7 feet above operating modules that cast a shadow over the long dimension of the cells. Close 
objects like posts, ropes, signs, fences, or equipment can begin to increase risk of partial shading of full cells when nearer 
than ~5-7 feet from the sunny-side of operating module. 

 
3.

 

A support frame or mounting method on the short edge(s) of modules that fully shades the entire length of a cell (either 
partially or completely). 

 
4.

 

Working continuously with outstretched arms or tools over operating modules. 

 
5.

 

Cleaning apparatus, including cleaning robots and other mechanisms that traverse the module repeatedly while the 
system is operating (unless evaluated and approved by First Solar). 

 
 

PD-5-200-04 NA | REV 3.1 | 0348_UG_NA_11JUL17 

Chosen Techno Solar Private Limited 

Summary of Contents for FS-4100

Page 1: ...User Guide User Guide Chosen Techno Solar Private Limited Series 4 Module North America REV 3 1 PD 5 200 04 NA 0348_UG_NA_11JUL17...

Page 2: ...1 System Derating Factors 5 4 Installation 6 4 1 Mounting 6 4 2 Module Orientation 8 4 3 Module Shading Considerations 8 4 4 Electrical Interconnection 9 5 Mechanical Specifications Drawings 12 6 Prop...

Page 3: ...lers and maintenance personnel Read this User Guide thoroughly before beginning any work related to the installation operation or maintenance of the Chosen Techno Solar Private Limited Series 4 or Ser...

Page 4: ...Chosen Techno Solar Private Limited module reverse current overload may result in module failure including module breakage Extreme and continuous reverse current overload conditions may cause a fire...

Page 5: ...ized or Listed by Underwriters Laboratories UL for their intended purpose Ensure the PV array open circuit voltage does not exceed 1500VDC 1000VDC for UL Canada Install modules with mounting systems t...

Page 6: ...2 FS 4105 2 FS 4107 2 FS 4110 2 FS 4112 2 FS 4100A 2 FS 4102A 2 FS 4105A 2 FS 4107A 2 FS 4110A 2 FS 4112A 2 Nominal Power 5 PMPP W 100 0 102 5 105 0 107 5 110 0 112 5 Voltage at PMA X VMPP V 66 2 67...

Page 7: ...tage VSYS V 1500 2 Maximum Series Fuse ICF A 4 0 1 As received and stabilized ratings at Standard Test Condition 1000W m2 AM 1 5 25 C Cell Temperature 10 2 1000V Listed for UL Canada 3 Measurement unc...

Page 8: ...d using approved hardware in the manner specified by the mounting instructions in Chosen Techno Solar Private Limited Application Note PD 5 320 04 NA Additional mounting systems may be approved for us...

Page 9: ...eight is 3 25 in 82 55 mm Modules used in UL Listed rooftop applications must be installed with approved mounting systems If alternate mounting means are employed this may affect the Listing fire clas...

Page 10: ...from diffuse shading for objects greater than 2 meters or 7 feet There is a low risk of module damage due to shading from walking or standing in front of operating modules or from parking or driving...

Page 11: ...lead wires tight at any time After installation the connected wire must not be under stress or tension Do not use junction box assembly or lead wire strain relief loops to secure excess wire or to be...

Page 12: ...re inverter ratings are appropriate When connecting Chosen Techno Solar Private Limited Series 4 and or Series 4A Modules in a series string ensure that the system design voltage and inverter design s...

Page 13: ...unded ungrounded floating and bi polar system architectures provided all appropriate design requirements are met and approved by First Solar FS Series PV Modules should not be used in positive grounde...

Page 14: ...on Span2 1314 mm 51 73 in Weight 12 kg 26 5 lbs Fire Performance Type3 Type 10 Module Class A Spread of Flame Class B Burning Brand Operating Temperature 40 C to 85 C 1Minimum from strain relief to co...

Page 15: ...ng in landscape orientation is acceptable Module row to row shading in portrait orientation is prohibited Strain relief cable ties must not be removed If module cleaning is undertaken modules must be...

Page 16: ...visit www firstsolar com recycling for further details on the recycling program It is normal for the modules to exhibit visual irregularities which do not impact power Series 4A Modules with anti refl...

Page 17: ...otice Accordingly the reader is cautioned to verify that data sheets are current before placing orders or finalizing system permitting and or design Information furnished by Chosen Techno Solar Privat...

Page 18: ...Series 4 PV Module Mounting for UL Applications PD 5 308 FS Series PV Modules Reverse Current Overload PD 5 320 04 FS Series 4 PV Module Mounting PD 5 804 FS Series PV Module Cleaning Guidelines PD 5...

Page 19: ...to 2 2 Section 4 1 1 Added comment to Section 7 on cleaning risk of damage 12 17 2017 Added Section 10 for Doc References Revised order of Warnings in Sections 2 3 Added electrical ratings for FS 4xx...

Reviews: