background image

WWW.CURRENT-USA.COM

Display

 

E1

E2

EP

EE

CL

Error Message

 

Appears when either the up or 
downkey is pressed when not in the 
programming mode.

Appears if the control settings are 
not properly stored in memory.

Appears when the probe is open, 
shorted or sensing a temperature 
that is out of range.

Appears if the EPROM dada has  
been corrupted.

Appears if calibration mode has  
been entered.

To Correct

If the E1 message appears even when 
no keys are being pressed, replace 
control.

Check all settings and correct if 
necessary.

Check to see if the sensed temperature 
is out of range. If not, check for 
probe damage by comparing it to a 
known ambient temperature between 
-30°F and 220°F. Replace the probe if 
necessary.
This condition cannot be field 
repaired. Replace the control.

Remove power to the control for at 
least five seconds. Reapply power. If 
the CL message still appeared, replace 
the control.

troubleshooting/

maintenance

Maintenance

  Your  Prime  Chiller,  if  installed  correctly,  should  provide  years  of  service  with  a  minimal 

amount of maintenance.

 

For proper maintenance:

1. Clean the condenser (radiator) fins regularly. Using a vacuum and soft brush attachment, 

remove lint, dust and animal fur at least once a month to allow for optimal heat removal and to 
prevent the compressor and electrical components from overheating. It is also recommended 
once every 3 months to remove the cover and clean the condenser fins on the inside of the 
unit where the fan is located. Debris can migrate inside of the unit where it may not be able 
to be reached from the outside.

2. Periodically inspect all fittings for leakage. Although most aquarists typically do inspect all 

their fittings once in a while, it is important to inspect the fittings attached to the chiller 
as leaking water (particularly salt water) can damage the components of the chiller if not 
discovered.

3. Periodically flush the evaporator. The refrigerant coils inside the evaporator housing can trap 

organic debris as well as become coated with mineral deposits such as calcium (especially 
with saltwater reef systems). It is recommended that the chiller be removed from service once 
a year and the evaporator flushed with freshwater. In addition, circulating a diluted hard 
water stain remover through the evaporator will help remove deposits that can affect the 
chiller’s performance. Be sure to rinse well with freshwater and let dry before re-installing 
the chiller on your system.

Summary of Contents for Prime Chiller 2604

Page 1: ...Stage Thermostat 2604 2606 Dual Stage Thermostat 2614 2616 Single Stage Thermostat w TXV 2626 2627 Warning and Safety Instructions Page 2 Chiller Installation Page 4 Temperature Controller Installati...

Page 2: ...t at www current usa com In the event that you are experiencing trouble running your chiller please visit our website support section at www current usa com or contact Current USA directly at 866 276...

Page 3: ...cord or plug or if it is malfunctioning or has been dropped or damaged in any manner If you are using the ultraviolet sterilizer or heater upgrade do not operate the unit without continual water flow...

Page 4: ...t the controller into 120V wall outlet and check to make sure that both the fan and compressor come on Do not leave chiller plugged in for more than 2 minutes 2 The temperature sensor for the controll...

Page 5: ...of one another See diagram below Either port can be used as the inlet or outlet depending upon the location of the chiller and plumbing configuration The ports will accept 1 male pipe thread MPT fitt...

Page 6: ...all the sensor into this port may cause an inaccurate temperature reading and in the event of low or no water flow may cause damage to the chiller Locate and install the temperature sensor for the con...

Page 7: ...rature and resume the normal operating mode 5 Press the SET key again to access the heater set point The LCD displays the set point and S2 will be blinking on and off indicating it is in the heat set...

Page 8: ...ng a vacuum and soft brush attachment remove lint dust and animal fur at least once a month to allow for optimal heat removal and to prevent the compressor and electrical components from overheating I...

Page 9: ...ged by accident abuse misuse or misapplication or if the product has been modified without the written permission of Current USA Inc or if any Current USA Inc logos have been removed or defaced THE WA...

Reviews: