I.B. 17555
Page 7
Effective 03/97
Table 2.2 Characteristic for Phase Element
CURVE SHAPE
IT, I
2
T, I
4
T, FLAT, MOD, VERY, XTRM,
IECA, IECB, IECC, IECD
INVERSE TIME OVERCURRENT
0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50,
+ 5%
PICKUP
0.55, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85,
0.90, 0.95, 1.00, 1.10, 1.20, 1.30, 1.40,
1.50, 1.60, 1.70, 1.80, 1.90, 2.00, 2.10,
2.20
INVERSE TIME OVERCURRENT
Curve = IT, I
2
T, I
4
T:
TIME MULTIPLIER
0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50,
+10%
➀ ➁
IT SC-5392-92B
0.55, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85,
I
2
T SC-5391-92B
0.90, 0.95, 1.00, 1.25, 1.50, 1.75, 2.00,
I
4
T SC-5390-92B
2.25, 2.50, 2.75, 3.00, 3.50, 4.00, 4.50,
5.00, 5.50, 6.00, 6.50, 7.00, 7.50, 8.00,
8.50, 9.00, 10.0, 12.5, 15.0, 17.5, 20.0,
22.5, 25.0, 27.5, 30.0, 35.0, 40.0
Curve = FLAT:
0.20, 0.25, 0.30, 0.35, 0.40, 0.45, 0.50,
+ 0.05 SEC
FLAT
0.55, 0.60, 0.65, 0.70, 0.75, 0.80, 0.85,
SC 5393-92B
0.90, 0.95, 1.00, 1.25, 1.50, 1.75, 2.00
Curve = ANSI MOD, VERY, XTRM:
+10%
➀ ➂
MOD SC-6685-96
0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9,
VERY SC-6686-96
1.0, 1.1, 1.2, 1.3, 1.4, 1.5, 1.6, 1.7, 1.8,
XTRM SC-6687-96
1.9, 2.0, 2.1, 2.2, 2.3, 2.4, 2.5, 2.6, 2.7,
2.8, 2.9, 3.0, 3.1, 3.2, 3.3, 3.4, 3.5, 3.6,
3.7, 3.8, 3.9, 4.0, 4.1, 4.2, 4.3, 4.4, 4.5,
4.6, 4.7, 4.8, 4.9, 5.0
Curve = IECA, IECB, IECC, IECD:
+10%
➀ ➂ ➃
IECA SC-6688-96
0.05, 0.10, 0.15, 0.20, 0.25, 0.30, 0.35,
IECB SC-6689-96
0.40, 0.45, 0.50, 0.55, 0.60, 0.65, 0.70,
IECC SC-6690-96
0.75, 0.80, 0.85, 0.90, 0.95, 1.00
IECD SC-6691-96
SHORT DELAY PICKUP
1.00, 1.25, 1.50, 1.75, 2.00, 2.25, 2.50,
+ 10%
SC-5394-92B
2.75, 3.00, 3.50, 4.00, 4.50, 5.00, 5.50,
6.00, 6.50, 7.00, 7.50, 8.00, 8.50, 9.00,
9.50, 10.0, 11.0, NONE
SHORT DELAY TIME
0.05, 0.10, 0.15, 0.20, 0.25, 0.30, 0.35,
+ 0.05 SEC
SC-5394-92B
(In Seconds)
0.40, 0.45, 0.50, 0.55, 0.60, 0.65, 0.70,
0.75, 0.80, 0.85, 0.90, 0.95, 1.00, 1.25,
1.50
INSTANTANEOUS PICKUP
1.00, 1.25, 1.50, 1.75, 2.00, 2.25, 2.50,
+ 10%
SC-5396-92B
2.75, 3.00, 3.50, 4.00, 4.50, 5.00, 5.50,
6.00, 6.50, 7.00, 7.50, 8.00, 8.50, 9.00,
9.50, 10.0, 12.5, 15.0, 17.5, 20.0, 22.5,
25.0, NONE
DISCRIMINATOR
D ON Fixed At 11 x I
n
+ 10%
(If Phase INST set to NONE)
D OFF
NOTES:
➀
Curves go to constant operating time above 30 x I
n
.
➁
Tolerance: ± 10% or 0.09 seconds, whichever is larger. Minimum operating trip time is 0.05 seconds.
➂
Tolerance: ± 10% or 0.09 seconds, whichever is larger (>1.5 x I
pu
). Minimum trip time is 2 power line cycles.
➃
For IECD, the Time Multiplier Tolerance is ±0.05 seconds.
TYPE SETTING
AVAILABLE SETTINGS
TOLERANCE
CURVE #