I.B. 29C891B
Page 24
Effective 11/98
TRIP UNIT TYPE
DIGITRIP OPTIM 1050
RMS Sensing
Yes
Programmable
Yes
CIRCUIT BREAKERS
Types
Series C K, L and N-Frames
»`
Series C R-Frames
SPB Pow-R
DSII/DSLII Power
Ampere Range
70 - 1200A
800 - 2500A
200 - 5000A
100 - 5000A
Interrupting Rating @ 480V
30 thru 100KA
65 thru 100KA
50 thru 150KA
30 thru 200KA
TRIP UNIT ORDERING OPTIONS
LSI
➀ ➁
No
Yes Yes
Yes
LSIG
➀ ➁
Yes
Yes
Yes
Yes
LSIA
➁
Yes
Yes
Yes
Yes
PROTECTION AND COORDINATION
Interchangeable Rating Plug (I
n
)
70-1200A
800-2500A
200-5000A
100-5000A
Over-Temperature Trip
Yes
Yes
Yes
Yes
LONG DELAY PROTECTION
Long Delay Setting (I
r
)
➂
0.4 - 1.0 x I
n
(0.01 steps)
0.4 - 1.0 x I
n
(0.01 steps)
0.4 - 1.0 x I
n
(0.01 steps)
0.4 - 1.0 x I
n
(0.01 steps)
Long Delay Pickup
116% of I
r
116% of I
r
116% of I
r
105% or I
r
Long Delay Time I
2
t @ 6 x I
r
➃
2-24 secs (0.10 steps)
2-24 secs (0.10 steps)
2-24 secs (0.10 steps)
2-24 secs (0.10 steps)
Long Delay Time I
4
t @ 6 x I
r
(SDT Slope Flat only)
➄
1-5 secs (0.10 steps)
1-5 secs (0.10 steps)
1-5 secs (0.10 steps)
1-5 secs (0.10 steps)
Long Delay Thermal Memory (Powered or Unpowered)
Yes (programmable)
Yes (programmable)
Yes (programmable)
Yes (programmable)
High Load Alarm
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
0.5 - 1.0 x I
r
SHORT DELAY PROTECTION
Short Delay Pickup
➂
1.5 - 8.0 x I
r
(0.1 steps)
1.5 - 8.0 x I
r
(0.1 steps)
1.5 - 8.0 x I
r
(0.1 steps)
1.5 - 10.0 x I
r
(0.1 steps)
(400 - 3000A)
1.5 - 6.0 x I
r
(0.1 steps)
(4000 - 5000A)
Short Delay Time I
2
t @ 8 x I
r
➅
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Short Delay Time Flat
➅
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Zone Selective Interlocking
Yes
Yes
Yes
Yes
INSTANTANEOUS PROTECTION
Instantaneous Pickup
➆
2.0 - 8.0 x I
n
(0.1 steps)
2.0 - 10.0 x I
n
(0.1 steps)
2.0 - 10.0 x I
n
(0.1 steps)
2.0 - 10.0 x I
n
(0.1 steps)
(1600 & 2000A)
(400 - 3000A)
2.0 - 6.0 x I
n
(0.1 steps)
2.0 - 6.0 x I
n
(0.1 steps)
(2500A)
(4000 & 5000A)
Discriminator
Yes
Yes
Yes
Yes
Override (Fixed Instantaneous)
➇
Yes
Yes
Yes
Yes
GROUND FAULT PROTECTION
Ground Fault Alarm (not to exceed 1200A)
➈
0.2 - 1.0 x I
s
(0.01 steps)
0.24 - 1.0 x I
n
(0.01 steps)
0.24 - 1.0 x I
n
(0.01 steps) 0.24 - 1.0 x I
n
(0.01 steps)
Ground Fault Pickup (not to exceed 1200A)
➆
0.2 - 1.0 x I
s
(0.01 steps)
0.24 - 1.0 x I
n
(0.01 steps)
0.24 - 1.0 x I
n
(0.01 steps) 0.24 - 1.0 x I
n
(0.01 steps)
Ground Fault Delay I
2
t @ 0.62 x I
n
/I
s
➉
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Ground Fault Delay Flat
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps)
0.1 - 0.5 secs (0.01 steps) 0.1 - 0.5 secs (0.01 steps)
Zone Selective Interlocking
Yes
Yes
Yes
Yes
Ground Fault Memory
Yes
Yes
Yes
Yes
SYSTEM MONITORING
Digital Display
Yes (Using OPT or BIM)
Yes (Using OPT or BIM)
Yes (Using OPT or BIM)
Yes (Using OPT or BIM)
Current
Yes
Yes
Yes
Yes
Cause of Trip LEDs
Yes
Yes
Yes
Yes
Magnitude of Trip Information
Yes
Yes
Yes
Yes
Remote Signal Contacts
Yes
Yes
Yes
Yes
Power and Energy
Yes
Yes
Yes
Yes
Power Quality - Harmonics
Yes
Yes
Yes
Yes
Power Factor
Yes
Yes
Yes
Yes
COMMUNICATIONS
IMPACC
Yes
Yes
Yes
Yes
TESTING
Testing Method
OPT, BIM, IMPACC
OPT, BIM, IMPACC
OPT, BIM, IMPACC
OPT, BIM,
Secondary Injection
Table 3.4 Digitrip OPTIM 1050 Trip Unit System Capabilities Overview
➀
No ground fault alarm (A) provided
➁
Refer to para. 3-2.3 and Figure 3-4 for details
➂
Setting Tolerance ±5%
➃
Setting Tol0-30%
➄
Setting Tol10-40%
Notes:
I
n
= Rating Plug
I
r
= Long Delay Setting
I
s
= Sensor Rating
OPT = Hand Held Programmer (OPTIMizer)
BIM = Breaker Interface Module
➅
Setting Tolerance (See time-current curves)
➆
Setting Tolerance ±10%
➇
Setting Tolerance ±20%
➈
Only available with LSIA
➉
I
s
(L & N-Frame), I
n
(R-Frame, SPB, DSII/DSLII)
Contact factory or Vista for K-Frame availability
11
11