background image

I.L. 29C508B

Page 6

Effective 9/00

The microcomputer, in cyclic fashion, repeatedly scans
the voltage values across each calibrating resistor and
enters these values into memory. These data are used
to calculate true RMS current values, which are then
repeatedly compared with the protection function set-
tings and other operating data stored in the memory.
The software program then determines whether to initi-
ate protection functions, including tripping the breaker
through the flux transfer shunt trip device in the circuit
breaker.

4.2  OVERLOAD TRIP

In accordance with standards requirements, the trip unit
initiates a trip of the circuit breaker within two hours for
an overload of 135 percent, and will trip in less time for
higher overload currents.

A "Thermal Memory" effect prevents the breaker from
being re-energized immediately after an overload. A
"cooling off" period of up to 5 minutes is required, which
allows time for cabling to cool off.

For details on the operation and protective functions of
the OPTIM 550 Trip unit and other related instructions,
contact Cutler-Hammer for the following information and
user’s manuals:

L-Frame and Accessories Selection Data

29-120L

Instructions and Overview of 

OPTIM Trip Units

29C890

Instructions on the Operation of Digitrip 

OPTIMIZER Hand Held Programmer

29C892

Instructions on the Operation of Digitrip 

Breaker Interface Module

29C893

Instructions on the Operation of Digitrip

OPTIM Trip Units

29C891

Digitrip OPTIM Wire Diagrams

29C894

5.0  TESTING

5.1  FUNCTIONAL FIELD TESTING

Any field testing should be done in accordance with
applicable NEMA Standard.  The operation of circuit
breakers with Digitrip OPTIM RMS trip units can be field
tested periodically using the hand held OPTIMIZER (see
user’s manuals).

5.2  PERFORMANCE  TESTING FOR GROUND
FAULT TRIP UNITS

5.2.1  CODE REQUIREMENTS

The National Electrical Code under Article 230-95-C
requires that any ground-fault protection system be per-

formance tested when first installed.  The test shall be
conducted in accordance with approved instructions 
provided with the equipment. A written record of this test
shall be made and shall be available to the authority
having inspection jurisdiction.

5.2.2  STANDARDS REQUIREMENTS

As a follow-up to the basic performance requirements
stipulated by the N.E.C. as stated above, UL Standard
No. 1053 requires that certain minimum instructions
must accompany each ground fault protection system.
These following statements plus a copy of the test
record form illustrated in Figure 5-4 are shipped with
each Digitrip OPTIM 550 Trip Unit.

5.2.3  GENERAL TEST INSTRUCTIONS

The interconnected system shall be evaluated in accor-
dance with the equipment assembler's detailed instruc-
tions by qualified personnel.

The polarity of the neutral sensor connections (if used)
must agree with equipment assembler's detailed instruc-
tions to avoid improper operations following apparently
correct simulated test operations. Where a question
exists, consult the specifying engineer and/or equipment
assembler.

The grounding points of the system shall be verified to
determine that ground paths do not exist that would
bypass the sensors. The use of high-voltage testers and
resistance bridges may be used.

THERE IS A HAZARD OF ELECTRICAL SHOCK OR
BURN WHENEVER WORKING IN OR AROUND
ELECTRICAL EQUIPMENT. ALWAYS TURN OFF
POWER SUPPLYING BREAKER BEFORE CON-
DUCTING TESTS.

Since the Digitrip OPTIM 550 Trip Units derive their
operating power from the phase currents, and not
from the neutral current, passing current through
the neutral sensor only will not properly test the
ground fault feature.

Using a low voltage (0-24 volt), high current, AC source,
apply a test current of 125% of the Digitrip OPTIM 550

!

WARNING

NOTICE

Summary of Contents for Digitrip OPTIM 550

Page 1: ...TY PROCEDURES CUTLER HAMMER IS NOT LIABLE FOR THE MISAP PLICATION OR MISINSTALLATION OF ITS PROD UCTS The user is cautioned to observe all recommendations warnings and cautions relating to the safety...

Page 2: ...DC applications a thermal magnetic trip unit should be used The Digitrip OPTIM 550 Trip Unit for the L Frame is available in 3 different types and four different maximum ampere ratings Table 1 1 Groun...

Page 3: ...ring channels Ground fault trip units are supplied from the factory with a wire harness with pigtail lead connections for a neutral current sensor white and gray wires A neutral current sensor is prov...

Page 4: ...etaining slots of the trip unit I L 29C508B Page 4 Effective 9 00 Figure 3 3 Neutral Current Sensor Placement 1 50 Table 3 1 Digitrip L Frame OPTIM Rating Plugs Max Amps In Catalog Number of trip unit...

Page 5: ...ed to avoid exceeding a safe terminal temperature operating range Consult Cutler Hammer for recommendations 4 1 GENERAL The Digitrip OPTIM 550 Trip Unit provides a tripping sig nal to the flux transfe...

Page 6: ...RFORMANCE TESTING FOR GROUND FAULT TRIP UNITS 5 2 1 CODE REQUIREMENTS The National Electrical Code under Article 230 95 C requires that any ground fault protection system be per formance tested when f...

Page 7: ...TING AND NOT FIELD CALIBRATION OF THE DIGITRIP OPTIM 550 GROUND FAULT TRIP UNIT ANY TEMPORARY CONNECTION MADE FOR THE PURPOSE OF CONDUCTING TESTS SHOULD BE RESTORED TO PROPER OPERATING CONDITIONS BEFO...

Page 8: ...es which mount on the trip unit are available for use The number of the instruction leaflet covering the installation of each accessory is shown Alarm Signal Lockout ASL Switch I L 29C183 Auxiliary Sw...

Page 9: ...round Fault Test Record should be Retained by Those in Charge of the Building s Electrical Installation in order to be Available to the Authority having Jurisdiction Test Date Circuit Breaker Number R...

Page 10: ...I L 29C508B Page 10 Effective 9 00...

Page 11: ...I L 29C508B Page 11 Effective 9 00...

Page 12: ...Cutler Hammer Pittsburgh Pennsylvania U S A Effective 9 00 ISI Style 6603C85H03 Printed in U S A Page 12 I L 29C508B...

Reviews: