Keltron Dialer guide
The Keltron SDACT Programmer and
Manual
are on your Keltron
CD
shipped with each unit. The Keltron ships
ready to be installed, no jumpers need to be changed. The Keltron will transmit
ONLY SIA
Code
, no Contact ID.
Reference
(4) Connections from CP-3000A/DA. CP-3000A/DA Alarm Zones A, B, C , & Trouble Contact to Dialer Zones
1,2,3, & 4 respectively.
(4) 10K EOL Resistors. (3) on Alarm Zones A,B,C, & (1) on Trouble Contact
(1) Connection from CP-3000A Trouble Input to Keltron Trouble Output
The Dialer Power Supply should be set to 24 Volts., change the jumper to the 24 volt setting.
Jumpers J4 through J8 should be closed.
If you need to change Zone 3 on the dialer from Alarm to Supervisory, remember to go into your Keltron
software and change your necessary Zone 3 Event Codes.
Open contacts on the dialer measure ~5 Vdc. Shorts will be 0vdc. A restored zone with a resistor will be
~2.5vdc.