TECHNICAL SPECIFICATIONS

 

 

 

 

10 

 

 

 

 

If the Battery module requires further service, please refer to the following information: 

1. Call us at (877) 297-6937 or write to us at Cyber Power Systems (USA), Inc., 4241 12th Ave. E., STE 400, Shakopee, MN 55379 or send us an e-mail 
message at tech@cpsww.com for instructions. 

2.  When  you  contact  CyberPower,  identify  the  Product,  the  Purchase  Date,  and  the  item(s)  of  Connected  Equipment.  Have  information  on  all  applicable 
insurance or other resources of recovery/payment that are available to the Initial Customer and Request a Claim Number. 

3. You must provide a dated Proof-of-Purchase receipt (or other proof of the original purchase) and provide a description of the defect. 

4. Pack and ship the product to CyberPower and, if requested, the item(s) of Connected Equipment, a repair cost estimate for the damage to the Connected 
Equipment, and all claim forms that CyberPower provides to you. Show the Claim Number on the shipping label or include it with the product.

 

You must prepay all shipping costs, you are responsible for packaging and shipment, and you must pay the cost of the repair estimate.

Model 

BP36V60ART2U 

BP72V60ART2U 

Configuration 

 

AC Input Voltage 

100~125Vac 

 

DC Output Voltage 

36Vdc 

72Vdc 

 

DC Output Current 

60A 

Physical 

 

Dimensions (L x W x H =) 

16.9 x 17 x 3.5in. (430 x 433 x 88mm) 

23.6 x 17 x 3.5in. (600 x 433 x 88mm) 

 

Net Weight 

50.6lbs(23.0Kg) 

96.8lbs(44.0Kg) 

Battery 

 

Specifications 

(6) (12V9AH) (2 x Banks of 3 Batteries) 

(12) (12V9AH) (2 x Banks of 6 Batteries) 

 

Replacement Battery Cartridge 

(1) RB1 (1) RB1290X3R 

(2) RB1290X6B 

 

Recharge Time 0-90% (Typical) 

4 hours 

 

Connector Type 

PP45 

 

Sealed, Maintenance Free 

Yes 

 

Hot-Swappable 

Yes 

 

Built-in Charger 

Yes (2A) max. 

Environment

 

 

Operating Temperature 

32

  to 104

  ( 0

  to 40

 

Operating Relative Humidity 

0 to 90% Non-Condensing 

Certifications

 

 

Safety 

UL1778, 

CSA C22.2 NO.107.3, 

FCC Part 15 Class B 

UL1778, 

CSA C22.2 NO.107.3, 

FCC Part 15 Class A 

 

Environmental 

RoHS compliant

 

Warranty

 

 

Product Warranty 

3-year limited warranty, Free Tech Support 

Problem

 

Possible Cause 

Solution

 

Warning 

BAT Disconnected 

Missing battery power. 

Check battery connector and battery breaker. 

Battery Failure 

UPS has failed a Battery Test. 

1.  Check battery connector and battery breaker. 
2.  Contact  technical  support  to  replace  the 

battery. 

Replace Battery 

Battery  will  soon  need  to  be  replaced  due  to 
insufficient runtime. 

Contact technical support to replace the battery. 

Fault

 

Over Charge 

Battery is overcharged. 

1.  Remove  battery  connector  and  check 

charger voltage. 

2.  Contact CyberPower for repair. 

Charger Failure 

Charger has failed. 

TROUBLE SHOOTING 

CUSTOMER SERVICE

 

 

 

Summary of Contents for BP36V60ART2U

Page 1: ... EXTENDED BATTERY MODULE EBM BP36V60ART2U BP72V60ART2U Cyber Power Systems USA Inc 4241 12th Avenue East Suite 400 Shakopee MN 55379 Phone 877 297 6937 Fax 952 403 0009 http www cyberpowersystems com K01 0000515 03 ...

Page 2: ...connection Additional parallel connected EBM provide the UPS for a longer extended runtime operation 1K 1 5KVA or 2K 3KVA extended battery module User s manual Register card Rackmount left rail Rackmount right rail Left hanging bracket Right hanging bracket IEC320 C14 to NEMA 5 15P power cord Rackmount ears Stands 2 Tie plate 1 M5X7L black flat head screws 8 M5X12L black pan head screws 12 M5X6L s...

Page 3: ...the mounting brackets RACKMOUNT INSTALLATION FOR 4 POST RACK Step 1 Remove the dust covers Remove the dust covers 5 pcs from the screw holes Step 2 Rackmount ears hanging brackets installation Attach two rackmount ears to the EBM using the provided M5X7L 8pcs screws and tighten two hanging brackets with the M5X6L 6pcs screws Step 3 Rackmount rail Installation The rails adjust to mount in 48 cm 19 ...

Page 4: ... the rear of the rack with two M5X12L screws and two plastic washers Step 5 Place and secure the EBM on the rails Slide the hanging brackets on the EBM into the rails mounted in the rack with the front of the unit facing toward you Secure the EBM to your rack with four M5X12L 4pcs screws at the front of the rack Located in position 2 position 5 How to slide the EBM out from the rack The EBM will b...

Page 5: ... strongly recommend having 2 3 people assist during the installation process CAUTION It is strongly recommended that the 2 post rack be bolted to the floor prior to the installation of the EBM Step 1 Remove side dust covers Remove seven dust covers from screw holes as shown below Step 2 Rackmount ears installation Attach the included rackmount ears to the center holes on the sides of the EBMEBM us...

Page 6: ...ew the upper panel of the UPS Separate the upper panel from the UPS Gently lift the LCD module out Rotate it to the tower orientation Reinstall it for a tower configuration SAFETY PRECAUTIONS CAUTION Installation environment should be in a temperature and humidity controlled indoor area free of conductive contaminants Do not install this EBM where excessive moisture or heat is present Please see s...

Page 7: ... EBM upstream 5 Input Connector Use this input connector to daisy chain the next EBM Remove the connector cover for access 6 Output Cable Use this output cable to connect the EBM to the UPS or to the next EBM 7 DC Breaker Use the DC breaker to disconnect battery output BP36V60ART2U BP72V60ART2U CONNECTION 1 UPS WITH ONE EXTENDED BATTERY MODULE Step 1 Turn off the DC breaker of the EBM Step 2 Loose...

Page 8: ...ry cable retention bracket and tighten the two screws to fix battery cable Step 6 Use a power cord to plug AC input inlet of the 2nd EBM into AC output outlet of the 1st EBM Step 7 Turn on the DC breaker of the 2nd Battery module Step 8 Set the EBM number to the respective setting to match the number of installed units To do this via the LCD control panel go to the Configuration Menu then scroll t...

Page 9: ...ect the Configure submenu 4 Press the and buttons to scroll to the EBM Number option 5 Press the ENTER button to select the EBM Number submenu The first configuration number will be displayed on the second column of LCD display 6 Press the and buttons to scroll through the number of attached EBM 7 Press the ENTER button to select the number of EBM installed You may be prompted to save the selectio...

Page 10: ...Replacement Batteries Please refer to the front side of the EBM for the model number of the correct replacement batteries For battery procurement log onto www cyberpowersystems com or contact your local dealer Battery Disposal Batteries are considered hazardous waste and must be disposed of properly Contact your local government for more information about proper disposal and recycling of batteries...

Page 11: ...ltage 100 125Vac DC Output Voltage 36Vdc 72Vdc DC Output Current 60A Physical Dimensions L x W x H 16 9 x 17 x 3 5in 430 x 433 x 88mm 23 6 x 17 x 3 5in 600 x 433 x 88mm Net Weight 50 6lbs 23 0Kg 96 8lbs 44 0Kg Battery Specifications 6 12V9AH 2 x Banks of 3 Batteries 12 12V9AH 2 x Banks of 6 Batteries Replacement Battery Cartridge 1 RB1290X3L 1 RB1290X3R 2 RB1290X6B Recharge Time 0 90 Typical 4 hou...

Page 12: ...ervice 1 Before contacting CyberPower identify Your Product model number and the Purchase Date 2 Email us at tech cpsww com or Call us at 877 297 6937 3 If your product requires warranty service you must provide a copy of your dated purchase receipt or invoice How Do You Open A Warranty Claim 1 Call us at 877 297 6937 or write to us at Cyber Power Systems USA Inc 4241 12th Ave E STE 400 Shakopee M...

Page 13: ...take Any Liability in Any Event for Any of the Following 1 Loss of or damage to data records or software or the restoration of data or records or the reinstallation of software 2 Damage from causes other than AC Power Line Transients spikes or surges on properly installed grounded and code compliant 120 volt power lines in the United States and Canada transients surges or spikes on standard teleph...

Page 14: ...no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be determined by turning the equipment off and on the user is encouraged to try to correct the interference by one or more of the following measures 1 Reorient or relocate the receiving antenna 2 Increase the separation between the ...

Reviews: