CONNECTION #2 : UPS WITH MULTIPLE EXTENDED BATTERY MODULES
Step 1: Connect the 1
st
EBM to the UPS using the instructions
above.
Step 2: Turn off the DC breaker of the 2
nd
Battery module.
Step 3: Loosen the two screws to remove the battery cable
retention bracket of the 1
st
EBM.
Step 4: Use the output cable of the 2
nd
EBM to connect the 2
nd
EBM to the 1
st
EBM.
Step 5: Rotate the battery cable retention bracket and tighten
the two screws to fix battery cable.
Step 6: Use a power cord to plug AC input inlet of the 2
nd
EBM
into AC output outlet of the 1
st
EBM.
Step 7: Turn on the DC breaker of the 2
nd
Battery module.
Step 8: Set the EBM number to the respective setting to match
the number of installed units. To do this via the LCD
control panel, go to the Configuration Menu, then scroll
to EBM Number setting, select the appropriate number
and Save. This operation can also be done if there is an
RMCARD installed in the UPS, or via PowerPanel®
Business Edition Agent. Please see their respective User
Manuals for instructions.