Table 6.1: Suggestion for Wire Selection
Rated Current of
Equipment (Amp)
Cross-section of Lead(mm
2
)
AWG
NOTE
10A ~ 13A
1.25
16
Choosing suitable wires based on
the rating of solar panels
and wiring length from the inverter
13A ~ 16A
1.5
14
16A ~ 25A
2.5
12
25A ~ 32A
4
10
32A ~ 40A
6
8
40A ~ 63A
10
6
Models using 48V batteries
63A ~ 80A
16
4
80A ~ 100A
25
2
Models using 24V batteries
100A ~ 125A
35
1
Models using 12V batteries
≥125A
50
0
(B) Suggested Battery Style and Capacity
Inverter
Battery Style
Lead-Acid Battery
Battery
Capacity
SA12
ESA12
SA24
ESA24
SA48
ESA48
12V / 120Ah ~ 12V / 400Ah
24V / 60Ah ~ 24V / 200Ah
48V / 30Ah ~ 48V / 100Ah
(C) Requirement of Installation: The unit should be mounted on a flat surface or holding
rack with suitable strength. To ensure the lifespan of the unit, it should be prevented
from operating in the environment of dust or moisture. This is a power supply with
inbuilt DC fan and please make sure a proper ventilation. (It is recommended to keep
at least 15cm clearance from the ventilating holes.)
Figure 6.1:
Example of Installation
EN
16
Summary of Contents for CPS1000
Page 1: ...OFF GRID INVERTER Instruction Manual CPS3000 CPS1500 CPS1000 CPS400 ...
Page 9: ...CPS3000SAxx CPS1500SAxx CPS1000SAxx CPS400SAxx EN 6 ...
Page 10: ...CPS3000ESAxx CPS1500ESAxx CPS1000ESAxx CPS400ESAxx EN 7 ...
Page 24: ...FR ONDULEUR HORS RESEAU Manuel d instructions CPS3000 CPS1500 CPS1000 CPS400 ...
Page 30: ...CPS3000SAxx CPS1500SAxx CPS1000SAxx CPS400SAxx FR 27 ...
Page 31: ...CPS3000ESAxx CPS1500ESAxx CPS1000ESAxx CPS400ESAxx FR 28 ...
Page 45: ...Note ...
Page 46: ...Note ...
Page 47: ...Note ...