23
Pmax
260W
Max. PV module numbers in series
1
→
36VDC÷30.9
Vmp
30.9V
Imp
8.42A
Max. PV module numbers in parallel
5
→
40A÷8.42
Total PV module numbers is 1×5=5
Voc
37.7V
Isc
8.89A
CAUTION!
Ensure that Open Circuit Voltage (Voc) of PV modules not exceeds 40V for
CPS1200EO12LCD and 55V for CPS2200EO24LCD, or else the product may be damaged.
If PV voltage or current is out of normal range, the unit will stop solar charging and send a warning