24
7 Specifications
Line Mode Specifications:
Table 7-1
INVERTER MODEL
CPS3000ECH48
CPS5000ECH48
Input Voltage Waveform
Sinusoidal (utility or generator)
Nominal Input Voltage
230VAC
Low Loss Voltage
170
±
5VAC(UPS) 90
±
5VAC(APL)
Low Loss Return Voltage
180
±
5VAC(UPS) 100
±
5VAC(APL)
High Loss Voltage
280
±
5VAC
High Loss Return Voltage
270
±
5VAC
Max AC Input Voltage
300VAC
Nominal Input Frequency
50Hz/60Hz (Auto detection)
Low Loss Frequency
40
±
1Hz
Low Loss Return Frequency
42
±
1Hz
High Loss Frequency
65
±
1Hz
High Loss Return Frequency
63
±
1Hz
Transfer Time
10ms (UPS) 20ms(APL)
Power derating:
When AC input voltage drops
to 170V depending on models,
the output power and charge
power will be derated.