25
Bat Mode Specifications:
Table7-2
INVERTER MODEL
CPS3000ECH48
CPS5000ECH48
Rated Output Power
3KVA/2.4KW
5KVA/4KW
Output Voltage Waveform
Pure Sine Wave
Output Voltage Regulation
230
±
5%VAC/208VAC/240VAC
Output Voltage Frequency
50Hz (default)/60Hz
Peak Efficiency
93.5%
Overload Protection
10s (110%-150%) 5s (150%-200%)
Battery Type
Lead_Acid
Battery Voltage Range
38.4V-60V (Lead_Acid)
Cold Start Voltage
46VDC (Lead_Acid)
High DC Cut-off Voltage
60VDC (Lead_Acid)
High DC Recovery Voltage
58VDC (Lead_Acid)
Low DC Warning Voltage
(only Lead_Acid)
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
44.0VDC
42.8VDC
40.4VDC
Low DC Warning Return
Voltage(only Lead_Acid)
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
46.0VDC
44.8VDC
42.4VDC
Low DC Cut-off Voltage
(only Lead_Acid)
@ load < 20%
@ 20% ≤ load < 50%
@ load ≥ 50%
42.0VDC
40.8VDC
38.4VDC
No Load Power Consumption
<50W
MAX Charging Current
100A
130A
MAX Charging Voltage
57.4VDC
Summary of Contents for CPS3000ECH48
Page 1: ...User s Manual All In One Off Grid Inverter ...
Page 2: ......
Page 33: ...Note ...
Page 34: ...Note ...
Page 35: ......