25
04
Power saving mode
enable/disable
Saving mode disable
(default)
If disabled, no matter connected load is low or
high, the on/off status of inverter output will
not be effected.
Saving mode enable
If enabled, the output of inverter will be off
when connected load is pretty low or not
detected.
05
Battery type
AGM (default)
User-Defined
If “User-Defined” is selected, battery charge
voltage and low DC cut-off voltage can be set
up in program 19, 20 and 21.
Flooded
Lithium (Only suitable when communicated with BMS)
06
Auto restart when overload
occurs
Restart disable
(default)
Restart enable
07
Auto restart when over
temperature occurs
Restart disable
(default)
Restart enable
08
Output voltage
230V (default)
220V
240V
208V
09
Output frequency
50Hz (default)
60Hz
10
Number of series
batteries connected
(e.g. Showing batteries are connected in 4 series)
11
Maximum utility
charging current
CPS5000ECH48A/CPS5000ECH48A-P: default 30A, 10A~60A Settable
CPS3000ECH48A: default 10A, 10A/15A Settable