27
20
Floating charging
voltage. If self-defined
is selected in program
5, this program can be
set up
default 54.0V, 48.0V~58.4V Settable
21
Low DC cut-off voltage.
If self-defined is
selected in program 5,
this program can be set
up
default 42.0V, 40.0V~48.0V Settable
22
Solar power balance.
When enabled, solar
input power will be
automatically adjusted
according to connected
load power.
Solar power balance
enable (Default):
If selected, solar input power will be
automatically adjusted according to the
following formula: Max. input solar power =
Max. battery charging power +
Connected load power.
Solar power balance
disable:
If selected, the solar input power will be the
same to max. battery charging power no
matter how much loads are connected. The
max. battery charging power will be based on
the setting current in program 2.
(Max. solar power = Max. battery charging
power)
23
AC output mode
*This
setting
is
only
available
when
the
inverter is in standby
mode (Switch off).
Single:
When the units are used in parallel with single
phase, please select “PAL” in program 23.
It requires 3 inverters to support
three-phase equipment, 1 inverter in each
phase. Please refers to 5-2 for detailed
information.
Please select “3P1” in program 23 for the
inverters connected to L1 phase, “3P2” in
program 23 for the inverters connected to L2
phase and “3P3” in program 23 for the
inverters connected to L3 phase.
Be sure to connect share current cable to
units which are on the same phase.
Do NOT connect share current cable between
units on different phases.
Besides, power saving function will be
automatically disabled.
Parallel:
L1 phase:
L2 phase:
L3 phase:
24
Allow neutral and
grounding of AC output is
connected together:
When enabled, inverter
can deliver signal to
trigger grounding box to
short neutral and
grounding
Disable: Neutral and grounding of AC output is disconnected.
(Default)
Enable: Neutral and grounding of AC output is connected.
This function is only available when the inverter is working with
external grounding box. Only when the inverter is working in battery
mode, it will trigger grounding box to connect neutral and grounding
of AC output.