Status
PV Panel
Battery
AC/On-Grid
Off-Grid
Explanation
Output
power from
PV and
battery
Output
power from
battery,
without PV
Green
Off
*A, *B
Off
(*C)
Orange
Off
Green
Green
Operating normally, supply
power from PV and battery to
loads
Green with
fast flashing
Operating normally with
battery
≧
75% and under
discharging
Orange with
fast flashing
(*C)
Orange
Off
Green
Operating normally with
battery 25~75% and under
discharging
Abnormal
condition or
fault
Abnormal
condition or
fault
Orange
Red with fast
flashing
(*C)
Orange
Off
Green
Operating normally with
battery <25% and under
discharging
Orange
Green
Off
(*A)
(*C)
Orange
Off
(*C)
Orange
Off
Off
PV panel voltage > 50V
(*A, *B)
Orange
Unit is operating with over
load, output power > 240W or
300VA
(*A)
Red
Unit is Off: A Fault, or
Over-Load, or Low-Battery
condition has Occurred
Red
Off
Battery Fault,
No battery or voltage is >
31Vdc
Red
Red
Low battery,
a. <20V if Pout > 100W
b. <21V if Pout 30-100W
c. <22V if Pout <30W
(*A) -> Color: depend on the remaining capacity.
(*B) -> Flashing frequency: charging is slow, discharging is fast.
(*C) -> If Off-Grid operation transfers from On-Grid mode and Grid is abnormal.